Toshiba BMS-TP0640ACE Manual page 80

Touch screen controller, tcs-net air conditioning control system
Table of Contents

Advertisement

• To change all the indoor addresses from an arbitrary wired remote controller;
(When the setup operation with automatic address has finished, this change is available.)
Contents : Using an arbitrary wired remote controller, the indoor unit address can be changed for each same
refrigerant system
∗ ∗ ∗ ∗ ∗ Change the address in the address check/change mode.
<Procedure> (Operation while air conditioner stops)
1
Push the timer time
Firstly, the line 1, item code
2
Using
+
UNIT
3
Push
button.
SET
• The indoor unit address, which is connected to the refrigerant system of the selected outdoor unit is
displayed and the fan is turned on.
First the current indoor address is displayed on the setup data. (Line address is not displayed.)
4
The indoor address of the setup data moves up/down by the timer time
Change the setup data to a new address.
5
Push
button to determine the setup data.
SET
6
Every pushing
displayed. Only fan of the selected indoor unit operates.
Repeat the procedure
7
Push
button.
SET
(All the displays on LCD go on.)
8
Push
button to finish the procedure.
SET DATA
1
SET
3
Here, if the unit No is not called up, the outdoor unit
in this line does not exist.
Push
button, and then select a line according to
CL
procedure 2 .
+
buttons simultaneously for 4 seconds or more.
(Address Change) is displayed.
buttons, select the line address.
button, the indoor unit numbers in the identical pipe are successively
UNIT
4
6
to
and change all the indoor addresses so that they are not duplicated.
CODE No.
UNIT No.
R.C. No.
UNIT
CL
Cancel of line selection
4
2
8
5, 7
To finish the setup
80
/
SET DATA
UNIT No.
R.C. No.
UNIT
SET
CL
Operation procedure
1
2
3
4
5
6
7
8
buttons.
CODE No.
6
End