General Notes; Printed Circuit Boards; Optical Components - ABB ACS880-207 Hardware Manual

Industrial drives, igbt supply units
Hide thumbs Also See for ACS880-207:
Table of Contents

Advertisement

5. Measure that the installation is de-energized. If the measurement requires removal or
disassembly of shrouding or other cabinet structures, obey the local laws and regulations
applicable to live working (including – but not limited to – electric shock and arc
protection).
• Before and after measuring the installation, verify the operation of the voltage tester
on a known voltage source.
• Make sure that the voltage between the drive input power terminals (L1, L2, L3) and
the grounding (PE) busbar is zero.
• Make sure that the voltage between the drive output terminals (T1/U, T2/V, T3/W)
and the grounding (PE) busbar is zero.
• Make sure that the voltage between the drive DC terminals (UDC+ and UDC-) and
the grounding (PE) terminal is zero. In cabinet-built drives, measure between the
drive DC busbars (+ and -) and the grounding (PE) busbar.
6. If the drive is not equipped with a grounding switch, install temporary grounding as
required by the local regulations.
7. Ask the person in control of the electrical installation work for a permit to work.

General notes

Printed circuit boards

WARNING!
Use a grounding wrist band when you handle printed circuit boards. Do not touch
the boards unnecessarily. The boards contain components sensitive to electrostatic
discharge.

Optical components

WARNING!
Obey these instructions. If you ignore them, damage to the equipment can occur.
• Handle the fiber optic cables with care.
• When you unplug the fiber optic cables, always hold the connector, not the cable itself.
• Do not touch the ends of the fibers with bare hands as the ends are extremely sensitive
to dirt.
• Do not bend the fiber optic cables too tightly. The minimum allowed bend radius is 35 mm
(1.4 in).
Electrical installation 47
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents