Electrical Power Network Specification; Control Unit Connection Data (Bcu) - ABB ACS880-207 Hardware Manual

Industrial drives, igbt supply units
Hide thumbs Also See for ACS880-207:
Table of Contents

Advertisement

132 Technical data

Electrical power network specification

Voltage (U
)
1
Network type
Frequency
Imbalance
Short-circuit withstand
strength (IEC/EN 61439-1)
Short-circuit current protec-
tion (UL 508A, CSA C22.2
No. 14-13)
Fundamental power factor
(cos phi
)
1
Harmonic distortion

Control unit connection data (BCU)

See chapter
The control
400 V units: 380...415 V AC 3-phase ± 10%. This is indicated in the type designation
label as typical input voltage level (3~ 400 V AC).
500 V units: 380...500 V AC 3-phase ± 10%. This is indicated in the type designation
label as typical input voltage levels (3~ 400/480/500 V AC).
690 V units: 525...690 V AC 3-phase ± 10% (525...600 V AC ± 10% in UL/CSA
installations, or corner-grounded TN systems). This is indicated in the type desig-
nation label as typical input voltage levels (3~ 525/600/690 V AC).
TN (grounded) and IT (ungrounded) systems
50/60 Hz, variation ± 5% of nominal frequency
Max. ± 3% of nominal phase-to-phase input voltage
Supply units with the ABB-defined main switch-disconnector and fuses:
•Rated peak withstand current I
•Rated short-time withstand current I
Supply units with ABB-defined main circuit breaker and fuses:
•Rated peak withstand current I
•Rated short-time withstand current I
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when the input cable is
protected with class T fuses.
0.99
Harmonics are below the limits defined in IEEE519.
R
sc
20
100
1) Other loads may influence the THD value.
THD = Total Harmonic Distortion (THD). The voltage THD depends on the short-
circuit ratio (R
). The spectrum of the distortion also contains interharmonics.
sc
R
= I
/I
sc
sc
N
I
= short-circuit current at point of common coupling (PCC)
sc
I
= IGBT supply unit nominal current
N
unit.
= 105 kA
pk
= 50 kA/1 s
cw
= 143 kA
pk
= 65 kA/1 s
cw
THD Voltage [%]
3
0.8
I
n
th
harmonic component
n
I
nominal current
N
THD Current [%]
1)
2.5
1)
2.5