Huawei PDU8000 User Manual page 54

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual (1100 mm Deep)
Figure 5-14 Not tied at bends
Figure 5-15 Extra length for easier plug and unplug
Figure 5-16 Stroking cables
Cable Layout
Table 5-6 Cable layout rules
No.
1
2
3
4
5
Issue 01 (2019-02-25)
Cable Layout Rule
The armoring layers of armored cables are grounded.
The PDC ground cable is secured to the equipment room ground bar. Use
a multimeter to measure the resistance between the PDC ground cable and
the equipment room ground bar, and verify that the reading is less than 0.1
ohm.
Cables are securely connected in the correct phase sequence.
Cables are neatly arranged, and cable insulation layers are intact.
Different types of cables are bound separately.
Copyright © Huawei Technologies Co., Ltd.