Huawei PDU8000 User Manual page 133

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual (1100 mm Deep)
Table 8-2 Routine maintenance for the PDC
Maintenance
Item
Three phase
power
indicators
Surge
protection
module
Liquid crystal
display (LCD)
screen on the
PDC
Connections of
input power
cables and
output power
cables
Signs of rodent
movements in
the PDC
PDC
component
appearance
Issue 01 (2019-02-25)
Maint
Operation
enanc
Guide
e
Interv
al
Monthl
Check the
y
luminance of
the indicators.
Monthl
Check the
y
status of the
surge
protection
module
indicator and
circuit breaker.
Monthl
Touch the LCD
y
screen with
your finger.
Monthl
Visual
y
observation
Monthl
Visual
y
observation
Quarter
Visual
ly
observation
Copyright © Huawei Technologies Co., Ltd.
Expected
Exception Handling
Result
The three
Replace the indicator that
phase power
generates no or dim light by
indicators
referring to
are steady
an
Indicator.
on.
The surge
If the indicator of an
protectio
SPD module is red,
n module
replace the SPD module
indicator
by referring to
is green.
Replacing an SPD
Module.
The
circuit
If the circuit breaker is
breaker is
switched off, switch it
switched
on.
on.
The LCD
Check whether the power
screen panel
cable is properly connected,
does not
and replace the LCD screen
display
if necessary by referring to
information
8.5.6 Replacing an
properly.
The
Take measures depending
cables are
on the severity.
not
damaged.
The
terminals
are intact
and
secure
and free
from
spark
signs and
rust.
There is no
If there is a sign of rodent
sign of
movements, ask a
rodent
professional for advice.
movements
in the PDC.
The exterior
Take measures depending
is intact.
on the severity.
8 Maintenance Guide
8.5.2 Replacing
8.5.1
MDU.
126