Huawei PDU8000 User Manual page 47

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual (1100 mm Deep)
Figure 5-5 Installing expansion sleeves
(1) M12 bolt
(4) Expansion sleeve
Step 7 Align the PDC mounting holes with the expansion bolt holes.
Step 8 Adjust the anchor bolts of the PDC using an adjustable wrench until the leveling feet touch
the floor.
Step 9 Level the PDC using a level and an adjustable wrench.
Issue 01 (2019-02-25)
Wrench a leveling foot clockwise to elevate the cabinet, or wrench a leveling foot anticlockwise to
lower the cabinet. The leveling feet can be adjusted within a range of 0–8 mm.
To prevent cabinet tilting, adjust all the feet at the four corners instead of one foot.
Do not remove anchor bolts, because this work brings you only a great deal of reworking.
Copyright © Huawei Technologies Co., Ltd.
(2) Spring washer
(5) Concrete floor
5 Installation Guide
(3) Flat washer
40

Advertisement

Table of Contents
loading

Table of Contents