PDU8000 Modular Precision Power Distribution Cabinet
User Manual (1100 mm Deep)
Figure 7-101 DIP switches
The following lists the functions of the DIP switches:
Table 7-3 Functions of the DIP switches
Function
Clear
historical
alarms.
Clear logs.
Restore
factory
settings.
Issue 01 (2019-02-25)
DIP1: Controls the CAN build-out resistor and is set to ON by default.
DIP2 to DIP4: Work together with specified buttons to clear historical records and logs
and restore factory settings.
To clear historical records and logs, you must log in as the admin user.
Status
Copyright © Huawei Technologies Co., Ltd.
DIP2
DIP3
DIP4
ON
OFF
OFF
OFF
ON
ON
ON
ON
OFF
7 MDU Commissioning Guide
Button
Action
Operation
Press and
Clear
hold Active
historical
Alarm for
alarms.
about 10s.
Press and
Clear
hold
operation
Buzzer Off
logs
for about
(APP/LUI).
10s.
The MDU
automatically
restarts
during the
process.
Press and
The MDU
hold
automatically
Buzzer Off
restarts after
for about
factory
10s.
settings are
restored.
124