Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 25

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:

Advertisement

Monitoring
Data
Device
Device Model
Device
Type
Name
Air
NetCol5000-
Collector_ECC
FE
Conditioner-
A025H412D2E120
800
D1
Collector_ECC
UPS5000-E-
FE
UPS-1
800
125K-HASBS
Collector_ECC
AI/DI
RS485
EN1MMEEM02A
800
Module-1
POLYMR M520/
Collector_ECC
Dry
Door Status
GREYSTONE GS-
800
contact
Sensor-1
Collector_ECC
Dry
FAULT
800
contact
RELAY
XT/K11031M2
POLYMR M520/
Collector_ECC
Dry
Door Status
GREYSTONE GS-
800
contact
Sensor-2
Collector_ECC
Dry
LOCAL
800
contact
FIRE
XT/K11031M2
Collector_ECC
Dry
FIRE
800
contact
RELAY
XT/K11031M2
GREYSTONE
Collector_ECC
Dry
Water
800
contact
Sensor-1
900D/POLYMRY
Collector_ECC
Dry
AC PDB-1
800
contact
SPD
Collector_ECC
Dry
Power PDB-
800
contact
1 SPD-1
Device IP
Device
Address
Address
N/A
N/A
E1
N/A
N/A
N/A
1
N/A
N/A
06
SIGMA
N/A
N/A
N/A
N/A
06
SIGMA
N/A
N/A
SIGMA
N/A
N/A
WD-
N/A
N/A
W517K
N/A
N/A
N/A
N/A
N/A
N/A
WebUI User
LCD User
Alarm
Name and
Name and
Threshold
Password
Password
User name:
Admin
N/A
N/A
Initial password:
000001
User name:
User name:
admin
Admin
N/A
Initial password:
Initial password:
Changeme
000001
N/A
N/A
N/A
Normal: closed
N/A
N/A
Alarm: open
Normal: open
N/A
N/A
Alarm: closed
Normal: closed
N/A
N/A
Alarm: open
Normal: open
N/A
N/A
Alarm: closed
Normal: open
N/A
N/A
Alarm: closed
Normal: closed
N/A
N/A
Alarm: open
Normal: closed
N/A
N/A
Alarm: open
Normal: closed
N/A
N/A
Alarm: open
Port to
Upper-
DDF
Upper-
Upper-
Level
Transfer
Level
Level
Device
Port
Device
Device
Port
Smart ETH
FE
N/A
POE_4
Gateway-2
Smart ETH
FE
N/A
POE_1
Gateway-3
Collector_
COM3/1
COM_IN
N/A
ECC800
2V
Crimped
Collector_
COM1/AI
N/A
terminal
ECC800
DI_4
Crimped
Collector_
N/A
AIDI_1 Extinguishant Control Panel
terminal
ECC800
Crimped
Collector_
COM2/AI
N/A
terminal
ECC800
DI_5
Crimped
Collector_
N/A
AIDI_2 Extinguishant Control Panel
terminal
ECC800
Crimped
Collector_
N/A
AIDI_3 Extinguishant Control Panel
terminal
ECC800
AI/DI
RJ45
N/A
AI/DI_1
Module-1
Crimped
AI/DI
N/A
AI/DI_2
terminal
Module-1
Crimped
AI/DI
N/A
AI/DI_3
terminal
Module-1
Remarks
Settings > Comm Settings >
IP Settings
Set IP assigning mode to
Automatic (DHCP).
Settings > Comm Settings >
IP Settings
Set IP assigning mode to
Automatic (DHCP).
Baud rate: 9600
Data bits: 8
Parity check bit: None
Stop bit: 1
N/A
N/A
N/A
N/A
N/A