Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 105

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:

Advertisement

NO.F002 Fire Extinguishing System Conceptual Diagram (CE) -1
+
-
E
Technical requirements:
1.
All fire extinguishing signal cables are red (BOM number: 25030029) and black (BOM number: 25030073) cables with naked crimping single-wire cord end terminals (BOM number: 14170214). The red cable is positive and the black cable is negative. The
pneumatic switch, Warning signs, and fire alarm bell each has two wiring terminals that connect to two wires. The fire alarm bell is polarity insensitive. For details, see the diagram.
2. Connect a 10K terminal resistor to each of the last the fire alarm sounder and fire alarm horn/strobe in parallel.
3. Connect cables to the smoke detector and heat detector by referring to the diagram. Connect a 6.8 K terminal resistor to the last smoke and heat detectors in parallel.
4. Connect the emergency abort button and pneumatic switch to a 6.8 K terminal resistor in parallel, and to a 470 ohm resistor in serial.
5. Alarm signals are reported to the monitoring system over shielded straight-through network cables. The connection definitions are as follows: LOCAL FIRE, FIRE RELAY, and FAULT RELAY. The signal cables connect to the ECC over
dry contacts.
6. Attach cable labels to all cables connected to the extinguishant control panel and wiring terminals on electrical actuators and pneumatic switches. See the label table for the label content. Cable direction labels must be arranged neatly in
the same direction. Cables must be bound neatly, with cable ties in the same direction. (Labels are printed on label paper with the BOM number 29041061, attached on cable ties with the BOM number 21200708, and bound to
corresponding cables.)
Terminal Resistor
Terminal Resistor
6.8K
6.8K
Terminal Resistor
10K
Fire Alarm Bell-1
red
black
red
red
10K
black
+
+
-
+
-
+
-
+
-
+
-
+
ROV
SIL
AL
FLT RST
AUX
S1
S2
ZONE 1
ZONE 2
REMOTE
DATA
POWER
CONTROL
STATUS UNITS
Data cable Power cable Connect the first
Connect smoke
Connect heat
stage alarm to the
detector in
detector in
fire alarm bell.
detection zone 1
detection zone 2
Warning Signs-1
I/P
COMM+ LEV1 LEV2
2WIRE
SILENCE
COMM+ LEV1 LEV2
Extinguishant Abort Button -1
2
6.8K
4
1
3
black
6.8K
6.8K
6.8K
red
black
red
black
-
+
-
+
-
+
-
+
-
+
NC
C
NO
NC
C
NO
1ST
ZONE 3
2ND
2ND
MODE
MAN
HOLD
SELECT
RELEASE
SOUNDER
STAGE
STAGE
Connect the
emergency
abort port to
Connect the second stage alarm
the extinguishant
abort button .
to the horn strobes and warning
signs .
Horn Strobes -2
Horn Strobes -1
Terminal Resistor
10K
- + +
- + +
I/P
SILENCE
2WIRE
pneumatic switch-1
NC
To Monitoring system
C
NO
Electrical Actuator-1
1
2
green
brown & white
green
green
brown & white
6.8K
red
black
red
black
-
+
-
+
-
+
-
NO
C
NC
C
NO
NC
C
NO NC
C
REL
EXTING
LOW
EXTRACT
FAULT
LOCAL
FIRE
PRESS
PRESS
RELAY
FIRE
RELAY
SWITCH
SWITCH
Connect the pressure
Connect the electrical
signal to the pneumatic
actuator drive signal to the
switch.
electrical actuator.
Connect the fault signal
Connect the gas release signal
Connect the fire alarm signal
output (NO) to the collector
output (NO) to the collector of
output (NO) to the collector
of the monitoring system.
the monitoring system.
of the monitoring system.
brown & white