ABB ACH580 Series Installation, Operation And Maintenance Manual page 94

Ultra-low harmonic drives
Hide thumbs Also See for ACH580 Series:

Advertisement

94
Basic control connections for E-Clipse HVAC Default
Parameter Number
*
Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in Smoke Control mode which may
reassign the function of the other Digital Inputs. Refer to the Smoke Control (Override1) documentation.
ACH580-3BCR/BDR
ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
ACH580 CONTROL BOARD
+
-
E-CLIPSE BYPASS CONTROL BOARD
X2
Parameters Changed Relative to E-Clipse HVAC Default
Terminal for Signal Cable Shield
1
Analog Input 1
2
Analog Input Common
3
+10V Reference Voltage for Potentiometer
4
Analog Input 2
5
6
Analog Input Common
7
Analog Output 1
8
Analog Output 2
9
Analog Output Common
X2
+24Vdc
1
+24Vdc
2
Digital Input Common
3
GND
4
Digital Input 1 (Parameter 1601)
5
Digital Input 2 (Parameter 1602,06)
6
Digital Input 3 (Parameter 1603)
7
Digital Input 4 (Parameter 1604,07)
8
Digital Input 5 (Parameter 1605, 1701) NOT SEL
9
Digital Input 6 (Fixed)
10
11
Relay Output 1 (parameter 1401) BYP NOT FLT
12
Default Operation: Bypass Not Faulted
13
14
Relay Output 2 (parameter 1404) SYS RUNNING
15
Default Operation: System Running
16
17
Relay Output 3 (parameter 1407) SYS STARTED
18
Default Operation: System started
19
20
Relay Output 4 (parameter 1410) BYPASS SEL
21
Default Operation: Bypass selected
22
23
Relay Output 5 (parameter 1413) BYPASS AUTO
24
Default Operation: Bypass auto
25
Description
START/STOP
NOT SEL
START INTERLOCK 1
NOT SEL
SMOKE CONTROL*
(OVERRIDE 1)
11 connected to 13
Bypass Faulted
11 connected to 12
14 connected to 16
17 connected to 19
20 connected to 22
23 connected to 25
Setting