2. Complete commissioning
Default configurations — HVAC and PID Control
For more information on Default configurations, see pages 31,
1
ACH580 Ultra-Low Harmonic Drives Installation
ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
This step is optional, and requires rotating the motor. Do
not do this if it could cause any risk, or if the mechanical
setup does not allow it.
To do the direction test, select Spin the motor and press
(Next).
Press the Hand key
Hand
Check the direction of the motor.
If it is forward, select Yes, motor is spinning forward
and press
(Next) to continue.
If the direction is not forward, select No, fix direction and
press
(Next) to continue.
The first start is now complete and the drive is ready for
use.
Press
(Done) to enter the Home view.
Press the Hand key to start the motor. The Home view is
shown on the panel. Select Menu (press on the soft key
under "Menu").
on the panel to start the drive.