ABB ACH580 Series Installation, Operation And Maintenance Manual page 86

Ultra-low harmonic drives
Hide thumbs Also See for ACH580 Series:

Advertisement

86
Installation – bypass
WARNING! When the ACH580 with E-Clipse Bypass is connected to the line power,
the Motor Terminals T1, T2, and T3 may be live even if the motor is not running. Do
not make any connections when the ACH580 with E-Clipse Bypass is connected to
the line. Disconnect and lock out power to the drive before servicing the drive.
Failure to disconnect power may cause serious injury or death.
1. Install wiring – bypass
WARNING!
• Metal shavings or debris in the enclosure can damage electrical equipment and
create a hazardous condition. Where parts, such as conduit plates require cutting
or drilling, first remove the part. If that is not practical, cover nearby electrical
components to protect them from all shavings or debris.
• Do not connect or disconnect input or output power wiring, or control wires, when
power is applied.
• Never connect line voltage to drive output Terminals T1, T2, and T3.
• Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of the
unit. Disconnect motor wires before taking any measurements in the motor or
motor wires.
• Make sure that power factor correction capacitors are not connected between the
drive and the motor.
ACH580-3BCR/BDR
ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual