ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
Default control connections for the HVAC default
Input Signals
1...10 kohm
max.
500 ohm
Notes:
1) Ground the outer shield of the cable 360 degrees under the grounding clamp on the grounding shelf for the control cables.
2) Connected with jumpers at the factory
3) Terminals 40 and 41 for external 24 V AC/DC input.
Terminal sizes:
R3: 24...14 AWG (0.2...2.5mm
26...16 AWG (0.14...2.5mm
R6...R8: 26...14 AWG (0.14...2.5mm
Tightening torques: 0.4 lb-ft (0.5...0.6 Nm)
Analog frequency/speed reference (AI1)
Start/stop selection (DI1)
Constant speed/frequency selection (DI3)
Start interlock 1 (DI4)
X1
Reference voltage and analog inputs and outputs
1
SCR
2
AI1
3
AGND
4
+10V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
1)
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
11
DGND
2)
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
Embedded fieldbus
29
B+
30
A-
31
DGND
S4
TERM
S5
BIAS
X4
Safe torque off
2)
34
OUT1
35
OUT2
36
SGND
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in Ext. 24V AC/DC input to power up the control unit
3)
41
24 V AC/DC- in
2
): Terminals +24V, DGND, DCOM, B+, A-, DGND, Ext. 24V
2
): Terminals DI, AI, AO, AGND, RO, STO
2
) (all terminals)
HVAC default direct I/O control
Output signals
Analog output AO1: Output frequency
Analog output AO2: Motor current
Relay output 1: Damper control
Relay output 2: Running
Relay output 3: Fault (-1)
ACH580 Ultra-Low Harmonic Drives Installation
Signal cable shield (screen)
Output frequency/speed reference: 0...10 V
Analog input circuit common
Reference voltage 10 V DC
1)
Actual feedback: 0...10 V
Analog input circuit common
Output frequency: 0...10 V
Output current: 0...20 mA
Analog output circuit common
Aux. voltage output +24 V DC, max. 250 mA
Aux. voltage output common
Digital input common for all
Stop (0) / Start (1)
Not configured
Constant frequency/speed selection
Start interlock 1 (1 = allow start)
Not configured
Not configured
Damper control
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
Embedded fieldbus, EFB (EIA-485)
Termination switch
Bias resistors switch
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
The Safe torque off function
on page 295.
when the main supply is disconnected.