4. Practical operations

4-1. Maintenance

4-1-1. Energy data output

The operation data of outdoor/indoor units and measurement data can be output to a USB memory device in a CSV
format.
Touch [Maintenance] in the menu bar, and then touch [Energy data output].
Refer to Table 4-1 "Energy Management Data List" and Table 4-2 "Data period" for details about the energy-control-
related items that can be output in a CSV format and how many months/years worth of data each CSV file can
contain.
Note: A separate license may be required to use the CSV output function. Only valid buttons can be selected on the screen.
Note: Use a USB memory device that meets the following conditions.
• Supports USB 2.0
• Formatted with FAT32 or FAT (FAT16)
• Security function is not provided or not required to be set.
Note: Test the USB memory device several times before use and verify that the device functions properly. Reading data from or
writing data to a USB memory device that has not been confirmed to work may cause unexpected problems. (If the data
cannot be output to the USB memory device after a writing error occurs and the device is replaced, reboot the AE-200/AE-50
(turn off the power and restart). Do not use the USB memory device that has experienced writing error once.)
Note: Ensure the CSV file is read with Microsoft
well as more than 256 rows, and use of Microsoft
Note: File names, as well as date formats, delimiter characters, and temperature units (°C, °F) within the files output as CSV will
use formats set as initial settings. Refer to the Instruction Book (Initial Settings) for settings methods.
Controller
Select [AE] to output the
data for AE-200, and
select [1], [2], [3], or [4] to
output the data for each
AE-50/EW-50.
Date range
Important
● The USB memory device may not be recognized if you insert and remove it within a short time. If this happens, reset the
AE-200/AE-50.
(1) Remove the controller cover, and insert a USB memory device to the USB port.
(2) Switch the [Controller] setting between [AE200] and [Exp1] through [Exp4] to output the data for each AE-200,
AE-50, and EW-50 individually.