NOTE
• Real sensorless vector control requires the following conditions.
If these conditions are not satisfied, select V/F control. Otherwise, malfunctions such as insufficient torque, uneven rotation
may occur.
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (Note that the motor
rated current should be 0.4 kW or higher (0.1 kW or higher for the 200 V class).)
If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies
may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
• Offline auto tuning is performed.
Offline auto tuning is required under Real sensorless vector control even when the Mitsubishi Electric motor is used since the
wiring length affects the operation.
• Single-motor operation (one motor to one inverter) is performed.
• A surge voltage suppression filter (FR-ASF/FR-BMF) is not used.
 PM sensorless vector control
• The inverter enables highly efficient motor control and highly accurate motor speed control of a PM (permanent magnet
embedded) motor, which is more efficient than an induction motor.
• A speed detector such as an encoder is not required as the inverter estimates the motor speed by the calculation from the
inverter output voltage and current. The inverter drives the PM motor with the least required current for a load in order to
achieve the highest motor efficiency.
PM sensorless vector control image
Inverter
Speed
command
Controller
Magnetic field observer
Speed/magnetic
pole position
NOTE
• The PM sensorless vector control requires the following conditions.
• For the motor capacity, the rated motor current should be equal to or less than the rated inverter current. (Note that the motor
rated current should be 0.4 kW or higher (0.1 kW or higher for the 200 V class).)
If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies
may deteriorate due to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
• Offline auto tuning is performed.
• Single-motor operation (one motor to one inverter) is performed.
• The overall wiring length with the motor must be 100 m or less. (For the wiring length, refer to the Instruction Manual
(Connection).)
• A surge voltage suppression filter (FR-ASF/FR-BMF) is not used.
Output
voltage
Inverter
circuit
*1
Output
current
Virtual motor
*1 A magnetic field observer is a control
method that calculates the motor
speed/magnetic pole position based
on the motor voltage and current of a
virtual motor which is set up in the
drive unit.
1
2
3
4
5
6
7
8
9
10
85