(2) Touch the "Temperature range" button to display the
settings screen.
Set the maximum and minimum temperatures for each
group.
For example, if [Control Time] is set to [01:00 - 05:00] and
"Temperature range" is set to [12°C - --°C] ([53°F - --°F]),
heating operation starts automatically when the room
temperature drops below the set temperature 12°C (53°F)
between 1:00 and 5:00. When the Setback Control ends at
5:00, the set temperature returns to the original setting, and
the operation stops.
Note: The air conditioning units in the heating operation will stop and the set temperature will return to the original setting
when the Setback Control period is over or the room temperature rises to the minimum temperature plus 3°C (6°F).
Likewise, the air conditioning units in the cooling operation will stop and the set temperature will return to the original
setting when the Setback Control period is over or the room temperature drops to the maximum temperature minus 3°C
(6°F).
(3) Touch [Save Settings].
WT07190X01
Room temp.
21°C (69°F)
Min. temp.
12°C (53°F)
Heat ON
Heat OFF
21°C (69°F)
When the temperature drops below the minimum temperature (heating operation)
Max. temp.
28°C (83°F)
Room temp.
24°C (75°F)
Cool ON
Cool OFF
24°C (75°F)
When the temperature rises above the maximum temperature (cooling operation)
Setback
operation
ends.
Setback
operation
starts.
Heat ON
Heat OFF
12°C (53°F)
21°C (69°F)
Setback Control period
Setback
operation
ends.
Setback
operation
starts.
Cool ON
Cool OFF
28°C (83°F)
24°C (75°F)
Setback Control period
98
3°C (6°F)
3°C (6°F)