5-3. Function1

5-3-1. Measurement
Measurement settings must be made to use temperature sensors, humidity sensors, and metering devices.
Touch [Function1] in the menu bar, and then touch [Measurement]. Set the measurement settings for each AE-200
and AE-50, and then touch [Save Settings].
Note: The measurement settings may not be accessible if logged in as a building manager.
Note: If the system is connected to a TG-2000A, make or change the settings from the TG-2000A.
Note: The [Controller] setting will appear when the [System Exp] setting on the [Unit Info.] screen is set to [Expand]. Switch the
[Controller] setting between [AE200], [AE1], [AE2], and [AE3] to make settings for each AE-200 and AE-50 individually.
Important
● Measurement settings for the AE-50 must be made with the AE-50 properly connected to ensure proper settings. Those
settings made without the connection of AE-50 will not be reflected.
Controller
Select [AE200] to make
settings for AE-200, and
select [AE1], [AE2], or [AE3]
to make settings for each
AE-50.
M-NET address of AI or PI
controller
Selection of AI or PI
controller
[1] Registering AI controllers and temperature/humidity sensors
Follow the instructions below to make the system settings for measurement sensors. Up to two measurement
sensors can be connected to an AI controller (PAC-YG63MCA).
Sensor name
AI controller icon
Setting details of sensor 1
Setting details of sensor 2
Temperature or humidity
sensor settings
(1) Using the scroll bar, select the address to which the AI controller (PAC-YG63MCA) will be connected.
(2) Select the AI controller icon (
Note: Touch again to deselect.
WT07190X01
Measurable range
Offset value
).
91
Scroll bar
Slide to show the address to
which the AI or PI controller
will be connected.
Setting details
Save Settings
Touch to save the changes
made.
Upper/lower ON- and OFF-
threshold settings for
e-mail alarm function
Upper limit
(ON-threshold)
Upper limit
(OFF-threshold)
Lower limit
(OFF-threshold)
Lower limit
(ON-threshold)