Mitsubishi Electric AE-200A Instruction Book page 76

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(2) LAN1 settings for connecting the AE-200/AE-50 to an existing LAN
(1) When connecting the AE-200/AE-50 to an existing LAN, consult the system administrator to decide the IP
addresses, subnet mask, and gateway addresses.
(3) LAN2 settings for connecting the AE-200/AE-50 to a dedicated LAN
(1) Change the LAN2 IP address only when the LAN1 IP address is required to be set to [192.168.2.1].
Note: Do not use the LAN2 port.
(4) LAN2 settings for connecting the AE-200/AE-50 to an existing LAN
(1) Change the LAN2 IP address only when the LAN1 IP address is required to be set to [192.168.2.1].
Note: Do not use the LAN2 port.
[2] M-NET Settings
Note: Make the M-NET settings only on the AE-200.
(1) Switch the [Controller] setting between [AE200], [AE1], [AE2], and [AE3] to make settings for each AE-200 and
AE-50 individually.
(2) Enter [0] in the [M-NET Address] field (unless otherwise specified).
(3) When the local remote controller operation is prohibited on the Web Browser for System Maintenance
Engineer, the [Range of Prohibited Controllers] setting determines the scope of its applicability. Select [SC/RC]
to prohibit the operation from both the sub system controllers and the remote controllers. Select [RC Only] to
prohibit the operation only from the remote controllers.
[3] External Input Setting
Using the external signal input function, the following types of collective operations can be performed for all
connected air conditioning units: Demand level, Emergency stop, ON/OFF operation, and Prohibit/Permit local
remote controller operation.
A separately-sold external input/output adapter (PAC-YG10HA-E) is required.
Note: Make the M-NET settings only on the AE-200.
Note: A separate license is required to activate demand control using the external input function. Make sure that the required
license has properly been registered on the [License] screen. (Refer to section 5-2-4 "License registration for optional
functions" for details.)
(1) Switch the [Controller] setting between [AE200], [AE1], [AE2], and [AE3] to make settings for each AE-200 and
AE-50 individually.
(2) Select [Demand (Level signal)/Not in use], [Emergency Stop (Level signal)], [ON/OFF (Level signal)], or [ON/
OFF/Prohibit/Permit (Pulse signal)]. Refer to the Installation Manual for details.
WT07190X01
76