Mitsubishi Electric AE-200A Instruction Book page 92

Air conditioning control system
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

(3) Touch the "Sensor name" button to display the keyboard. Enter the name of the sensor in 20 characters or
less.
Note: The following characters cannot be used: <, >, &, ", or '
(4) Touch the "Temperature or humidity sensor settings"
button to display the sensor settings screen.
Select the temperature sensor icon (
sensor icon (
(5) Touch the [Bottom] and [Top] buttons to display the
keypad. Enter the measurable range of the sensor, and
then touch [OK].
Note: The settable range for temperature sensor is between
-100.0ºC (-148.0ºF) and +100.0ºC (+212.0ºF), and for
the humidity sensor is between 0.0% and +100.0%.
Note: When the Pt sensor is connected, the range must be
between -30ºC (-22ºF) and +60ºC (+140ºF).
When the sensors other than the Pt sensors are
connected, enter the ranges that are described in the
operation manuals of the sensor.
(6) To set the offset value for the measured values, touch the [Offset] button to display the keypad. Enter the offset
value, and then touch [OK].
Note: The settable offset value range for temperature sensor is between -10.0ºC (-18.0ºF) and +10.0ºC (+18.0ºF), and for the
humidity sensor is between -10.0% and +10.0%.
(7) To receive an e-mail alarm when the temperature or the
humidity exceeds certain predetermined values, set the
ON- and OFF-thresholds for both the upper and lower
limit temperatures.
Touch the "Upper/lower ON- and OFF-threshold settings
for e-mail alarm function" section to display the settings
screen.
Touch the [U alarm ON]/[L alarm ON] and [U alarm OFF]/
[L alarm OFF] buttons to display the keypad. Enter the
ON- and OFF-thresholds for the upper and lower limit
temperatures, and then touch [OK].
Note: To clear the ON- and OFF-thresholds for the upper limit
temperatures, touch [U clear]. To clear the ON- and
OFF-thresholds for the lower limit temperatures, touch [L
clear].
Note: To avoid frequent ON/OFF cycling, the minimum
differential between the ON- and OFF-threshold values
should be 1ºC (2ºF).
(8) Touch [Save Settings].
WT07190X01
) or the humidity
).
Measurable range
Upper limit (ON-threshold)
Upper limit (OFF-threshold)
Lower limit (ON-threshold)
92
Selection of temperature or humidity
sensor icon
Offset value
Lower limit (OFF-threshold)