Power Supply Module - Mitsubishi Electric Melsec-Q172DCPU User Manual

Motion controller
Table of Contents

Advertisement

2 SYSTEM CONFIGURATION

2.5.2 Power supply module

Power supply modules specifications (Q61P-A1, Q61P-A2, Q61P, Q62P)
Item
Base loading position
Applicable base unit
Input power supply
Input frequency
Input voltage distortion factor
Max. input apparent power
Inrush current
5VDC
Rated output current
24VDC
External output voltage
5VDC
Overcurrent protection
(Note-1)
24VDC
Overvoltage protection
5VDC
(Note-2)
Efficiency
Allowable momentary power failure
(Note-3)
time
Dielectric withstand voltage
Insulation resistance
Noise durability
Operation indication
Fuse
Application
Rated switching
voltage/current
Minimum switching
Contact
load
output
Response time
section
Life time
Surge suppressor
Fuse
Terminal screw size
Applicable wire size
Applicable solderless terminal
Applicable tightening torque
Exterior dimensions[mm(inch)]
Mass [kg]
(1) Power supply module specifications
Q61P-A1
100 to 120VAC
(+10%/-15%)
(85 to 132VAC)
Across inputs/LG and outputs/FG, across inputs and LG, across outputs and FG 10M or more by
• By noise simulator of 1500Vp-p noise voltage, 1 µ s noise width and 25 to 60Hz noise frequency
• Noise voltage IEC 61000-4-4, 2kV
Electrical : 100 thousand times or more at rated switching voltage/current
Q61P-A2
Q series power supply module loading slot
Q35DB, Q38DB, Q312DB, Q63B, Q65B, Q68B, Q612B
200 to 240VAC
(+10%/-15%)
(170 to 264VAC)
50/60Hz ±5%
5% or less
105VA
20A 8ms or less
6A
——
——
6.6A or more
——
5.5 to 6.5V
70% or more
20ms or less
2300VAC per minute (Altitude 0 to 2000m (0 to 6561.68ft.))
Across inputs/LG and outputs/FG
insulation resistance tester (500VDC)
LED indication (Normal : ON (Green), Error : OFF)
Built-in (Unchangeable by user)
ERR. contact
24VDC, 0.5A
5VDC, 1mA
OFF to ON: 10ms or less, ON to OFF: 12ms or less
Mechanical : 20 million times or more
None
None
M3.5 screw
0.75 to 2mm
RAV1.25 to 3.5, RAV2 to 3.5, thickness of 0.8mm or less.
Two solderless terminals can be connected to one terminal.
0.66 to 0.89 N•m
98(H) × 55.2(W) × 90(D) (3.86(H) × 2.17(W) × 3.54(D) )
0.31
2 - 46
Q61P
100 to 240VAC (+10%/-15%)
(85 to 264VAC)
130VA
(Note-4)
24VDC±10%
3.3A or more
0.66A or more
65% or more
2
0.40
Q62P
105VA
3A
0.6A
0.39

Advertisement