E.2.1 Implementation Table - GE UR Series Instruction Manual

Line differential relay
Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

E.2 DNP IMPLEMENTATION TABLE
E.2 DNP IMPLEMENTATION TABLE
The following table identifies the variations, function codes, and qualifiers supported by the UR in both request messages
and in response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or
28. For change-event objects, qualifiers 17 or 28 are always responded.
Table E–2: IMPLEMENTATION TABLE (Sheet 1 of 4)
OBJECT
OBJECT
VARIATION
DESCRIPTION
NO.
NO.
1
0
Binary Input (Variation 0 is used to request
default variation)
1
Binary Input
2
Binary Input with Status
(default – see Note 1)
2
0
Binary Input Change (Variation 0 is used to
request default variation)
1
Binary Input Change without Time
2
Binary Input Change with Time
E
(default – see Note 1)
10
0
Binary Output Status (Variation 0 is used to
request default variation)
2
Binary Output Status
(default – see Note 1)
12
1
Control Relay Output Block
20
0
Binary Counter
(Variation 0 is used to request default
variation)
1
32-Bit Binary Counter
(default – see Note 1)
Note 1:
A Default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Type 30 (Analog
Input) data is limited to data that is actually possible to be used in the UR, based on the product order code. For example, Signal
Source data from source numbers that cannot be used is not included. This optimizes the class 0 poll data size.
Note 2:
For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3:
Cold restarts are implemented the same as warm restarts – the UR is not restarted, but the DNP process is restarted.
E-4
REQUEST
FUNCTION
QUALIFIER
CODES (DEC)
CODES (HEX)
1
00, 01
(read)
22
06
(assign class)
(no range, or all)
07, 08
17, 28
1
00, 01
(read)
22
06
(assign class)
(no range, or all)
07, 08
17, 28
1
00, 01
(read)
22
06
(assign class)
(no range, or all)
07, 08
17, 28
1
06
(read)
(no range, or all)
07, 08
1
06
(read)
(no range, or all)
07, 08
1
06
(read)
( no range, or all)
07, 08
1
00, 01
(read)
06
(no range, or all)
07, 08
17, 28
1
00, 01
(read)
06
(no range, or all)
07, 08
17, 28
3
00, 01
(select)
4
07, 08
(operate)
5
17, 28
(direct op)
6 (
dir. op, noack)
1
00, 01
(read)
7
06
(freeze)
(no range, or all)
8
07, 08
(freeze noack)
9
17, 28
(freeze clear)
10
(frz. cl. noack)
22
(assign class)
1
00, 01
(read)
7
06
(freeze)
(no range, or all)
8
07, 08
(freeze noack)
9
17, 28
(freeze clear)
10
(frz. cl. noack)
22
(assign class)
L90 Line Differential Relay
APPENDIX E

E.2.1 IMPLEMENTATION TABLE

RESPONSE
FUNCTION
QUALIFIER
CODES (DEC)
CODES (HEX)
(start-stop)
(limited qty)
(index)
129
00, 01
(start-stop)
(response)
17, 28
see Note 2)
(limited qty)
(
(index)
129
00, 01
(start-stop)
(response)
17, 28
(see Note 2)
(limited qty)
(index)
(limited qty)
129
17, 28
(response)
130
(limited qty)
(unsol. resp.)
129
17, 28
(response
130
(limited qty)
(unsol. resp.)
(start-stop)
(limited qty)
(index)
129
00, 01
(start-stop)
(response)
17, 28
(see Note 2)
(limited qty)
(index)
129
echo of request
(start-stop)
(response)
(limited qty)
(index)
(start-stop)
(limited qty)
(index)
129
00, 01
(start-stop)
(response)
17, 28
(see Note 2)
(limited qty)
(index)
GE Power Management
(start-stop)
(index)
(start-stop)
(index)
(index)
(index)
(start-stop)
(index)
(start-stop)
(index)