APPENDIX D
6.
BASIC APPLICATION FUNCTIONS
Station Initialization:
Ë
Remote initialization
Cyclic Data Transmission:
Ë
Cyclic data transmission
Read Procedure:
Ë
Read procedure
Spontaneous Transmission:
Ë
Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of an information
object. The particular information object addresses for which double transmission is enabled are defined in a project-
specific list.
Ë
Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1
Ë
Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1
Ë
Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1
Ë
Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
Ë
Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1
Ë
Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1
Ë
Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
Ë
Global
Ë
Group 1
Ë
Group 2
Ë
Group 3
Ë
Group 4
Clock synchronization:
Ë
Clock synchronization (optional, see Clause 7.6)
Command transmission:
Ë
Direct command transmission
Ë
Direct setpoint command transmission
Ë
Select and execute command
Ë
Select and execute setpoint command
Ë
C_SE ACTTERM used
Ë
No additional definition
Ë
Short pulse duration (duration determined by a system parameter in the outstation)
Ë
Long pulse duration (duration determined by a system parameter in the outstation)
Ë
Persistent output
Ë
Supervision of maximum delay in command direction of commands and setpoint commands
Maximum allowable delay of commands and setpoint commands: 10 s
GE Power Management
Ë
Ë
Group 5
Ë
Ë
Group 6
Ë
Ë
Group 7
Ë
Ë
Group 8
L90 Line Differential Relay
D.1 IEC 60870-5-104 POINTS LIST
Ë
Group 9
Group 13
Ë
Group 10
Group 14
Ë
Group 11
Group 15
Ë
Group 12
Group 16
D
D-7