Load Encroachment - GE UR Series Instruction Manual

Line differential relay
Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
ÖØ
PATH: SETTINGS
GROUPED ELEMENTS

LOAD ENCROACHMENT

5
The Load Encroachment element responds to the positive-sequence impedance and applies a characteristic shown in the
figure below.
The element operates if the positive-sequence voltage is above a settable level and asserts its output signal that can be
used to block selected protection elements such as distance or phase overcurrent. The following figure shows an effect of
the Load Encroachment characteristics used to block the QUAD distance element.
5-78
Ö
SETTING GROUP 1(8)
LOAD ENCROACHMENT
FUNCTION: Disabled
LOAD ENCROACHMENT
MESSAGE
SOURCE: SRC 1
LOAD ENCROACHMENT
MESSAGE
MIN VOLT: 0.250 pu
LOAD ENCROACHMENT
MESSAGE
REACH: 1.00 Ω
LOAD ENCROACHMENT
MESSAGE
ANGLE: 30°
LOAD ENCROACHMENT
MESSAGE
PKP DELAY: 0.000 s
LOAD ENCROACHMENT
MESSAGE
RST DELAY: 0.000 s
LOAD ENCRMNT BLK:
MESSAGE
Off
LOAD ENCROACHMENT
MESSAGE
TARGET: Self-reset
LOAD ENCROACHMENT
MESSAGE
EVENTS: Disabled
–REACH
LOAD ENCROACHMENT
OPERATE
Figure 5–34: LOAD ENCROACHMENT CHARACTERISTIC
L90 Line Differential Relay
ÖØ
LOAD ENCROACHMENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2,..., SRC 6
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.02 to 250.00 ohms in steps of 0.01
Range: 5 to 50° in steps of 1
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Flexlogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
X
REACH
LOAD ENCROACHMENT
OPERATE
827846A1.CDR
5 SETTINGS
5.5.9 LOAD ENCROACHMENT