APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 38)
ADDR
REGISTER NAME
7A53
Ground Distance Z2 Z0M Z1 Mag
7A54
Ground Distance Z2 Z0M Z1 Ang
7A55
Ground Distance Z2 Volt Level
Frequency (Read Only)
8000
Tracking Frequency
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
FlexElement (Read/Write Setting) (16 modules)
9000
FlexElement Function
9001
FlexElement Name
9004
FlexElement InputP
9005
FlexElement InputM
9006
FlexElement Compare
9007
FlexElement Input
9008
FlexElement Direction
9009
FlexElement Hysteresis
900A
FlexElement Pickup
900C
FlexElement DeltaT Units
900D
FlexElement DeltaT
900F
FlexElement Pkp Delay
9010
FlexElement Rst Delay
9011
FlexElement Block
9012
FlexElement Target
9013
FlexElement Events
9014
...Repeated for module number 2
9028
...Repeated for module number 3
903C
...Repeated for module number 4
9050
...Repeated for module number 5
9064
...Repeated for module number 6
9078
...Repeated for module number 7
908C
...Repeated for module number 8
90A0
...Repeated for module number 9
90B4
...Repeated for module number 10
90C8
...Repeated for module number 11
90DC
...Repeated for module number 12
90F0
...Repeated for module number 13
9104
...Repeated for module number 14
9118
...Repeated for module number 15
912C
...Repeated for module number 16
FlexElement Actuals (Read Only) (16 modules)
9A01
FlexElement Actual
9A03
...Repeated for module number 2
9A05
...Repeated for module number 3
9A07
...Repeated for module number 4
9A09
...Repeated for module number 5
9A0B
...Repeated for module number 6
9A0D
...Repeated for module number 7
9A0F
...Repeated for module number 8
9A11
...Repeated for module number 9
9A13
...Repeated for module number 10
9A15
...Repeated for module number 11
9A17
...Repeated for module number 12
9A19
...Repeated for module number 13
GE Power Management
RANGE
0 to 7
-90 to 90
0 to 5
2 to 90
---
0 to 1
---
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 1
0.1 to 50
-90 to 90
0 to 2
20 to 86400
0 to 65.535
0 to 65.535
0 to 65535
0 to 2
0 to 1
-2147483.647 to
2147483.647
L90 Line Differential Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
0.01
F001
°
1
F002
pu
0.001
F001
Hz
0.01
F001
---
---
F300
---
1
F102
---
---
F206
---
1
F600
---
1
F600
---
1
F516
---
1
F515
---
1
F517
%
0.1
F001
pu
0.001
F004
---
1
F518
---
1
F003
s
0.001
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
0.001
F004
DEFAULT
0
0
0
0
B
0
0 (Disabled)
"FxE \x040"
0
0
0 (LEVEL)
0 (SIGNED)
0 (OVER)
30
1000
0 (Milliseconds)
20
0
0
0
0 (Self-reset)
0 (Disabled)
0
B-33

Advertisement

Table of Contents
loading

This manual is also suitable for:

L90