APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 17 of 38)
ADDR
REGISTER NAME
5D08
Ground TOC1 Target
5D09
Ground TOC1 Events
5D0A
Reserved (6 items)
5D10
...Repeated for module number 2
5D20
...Repeated for module number 3
5D30
...Repeated for module number 4
5D40
...Repeated for module number 5
5D50
...Repeated for module number 6
Ground IOC (Read/Write Grouped Setting) (12 modules)
5E00
Ground IOC1 Signal Source
5E01
Ground IOC1 Function
5E02
Ground IOC1 Pickup
5E03
Ground IOC1 Delay
5E04
Ground IOC1 Reset Delay
5E05
Ground IOC1 Block
5E06
Ground IOC1 Target
5E07
Ground IOC1 Events
5E08
Reserved (8 items)
5E10
...Repeated for module number 2
5E20
...Repeated for module number 3
5E30
...Repeated for module number 4
5E40
...Repeated for module number 5
5E50
...Repeated for module number 6
5E60
...Repeated for module number 7
5E70
...Repeated for module number 8
5E80
...Repeated for module number 9
5E90
...Repeated for module number 10
5EA0
...Repeated for module number 11
5EB0
...Repeated for module number 12
L90 Trip Logic (Read/Write Grouped Setting)
5EE0
87L Trip Function
5EE1
87L Trip Source
5EE2
87L Trip Mode
5EE3
87L Trip Supervision
5EE4
87L Trip Force 3 Phase
5EE5
87L Trip Seal In
5EE6
87L Trip Seal In Pickup
5EE7
87L Trip Target
5EE8
87L Trip Events
Stub Bus (Read/Write Grouped Setting)
5F10
Stub Bus Function
5F11
Stub Bus Disconnect
5F12
Stub Bus Trigger
5F13
Stub Bus Target
5F14
Stub Bus Events
Disturbance Detector (Read/Write Grouped Setting)
5F20
DD Function
5F21
DD Non Cur Supervision
5F22
DD Control Logic
5F23
DD Logic Seal In
5F24
DD Events
Differential 87L (Read/Write Grouped Setting)
6000
87L Function
6001
87L Block
GE Power Management
RANGE
0 to 2
0 to 1
0 to 1
0 to 5
0 to 1
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0 to 65535
0 to 65535
0 to 1
0.2 to 0.8
0 to 2
0 to 1
0 to 1
0 to 65535
---
0 to 2
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 65535
L90 Line Differential Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F109
---
1
F102
---
1
F001
---
1
F167
---
1
F102
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F157
---
1
F300
---
1
F300
---
1
F102
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F300
DEFAULT
0 (Self-reset)
0 (Disabled)
0
B
0 (SRC 1)
0 (Disabled)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (3-Pole)
0
0
0 (Disabled)
20
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0
0 (Disabled)
0 (Disabled)
0