6 ACTUAL VALUES
VALIDITY OF CHANNEL CONFIGURATION:
The current state of the communications channel identification check, and hence validity, is displayed here. If a remote
relay ID number does not match the programmed number at the local relay, the "FAIL" value will be displayed. The "n/a"
value appears if the Local relay ID is set to a default value of "0" or if the 87L element is disabled. Refer to
ÖØ
SYSTEM SETUP
L90 POWER SYSTEM
PFLL STATUS:
This value represents the status of the Phase & Frequency Locked Loop Filter which uses timing information from local &
remote terminals to synchronize the clocks of all terminals. If
nized and 87L protection is enabled. If it is "FAIL", the clocks of all terminals are not synchronized and 87L protection is dis-
abled. If "n/a", then PFLL is disabled.
At startup, the clocks of all terminals are not synchronized and the PFLL status displayed is FAIL. It takes
approximately 1 to 2 minutes after startup for the value displayed to change from FAIL to OK.
NOTE
Ö
PATH: ACTUAL VALUES

DIGITAL COUNTERS

DIGITAL COUNTERS
Counter 1
MESSAGE
MESSAGE
MESSAGE
The present status of the 8 digital counters is shown here. The status of each counter, with the user-defined counter name,
includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date/time stamp
for the frozen count. The
Counter n MICROS
Ö
PATH: ACTUAL VALUES
STATUS

FLEX STATES

MESSAGE
There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit.
Ö
PATH: ACTUAL VALUES
STATUS

ETHERNET

MESSAGE
GE Power Management
section for more information
PFLL STATUS
ÖØ
DIGITAL COUNTERS
Counter 1
ACCUM:
0
Counter 1
FROZEN:
0
Counter 1
FROZEN:
YYYY/MM/DD HH:MM:SS
Counter 1
MICROS:
0
value refers to the microsecond portion of the time stamp.
ÖØ
FLEX STATES
PARAM
1: Off
Off
PARAM 256: Off
Off
ÖØ
ETHERNET
ETHERNET PRI LINK
STATUS: OK
ETHERNET SEC LINK
STATUS: OK
L90 Line Differential Relay
is "OK", the clocks of all terminals are synchro-
6.2.11 DIGITAL COUNTERS
Ö
DIGITAL COUNTERS Counter 1(8)
Range: Off, On
Range: Off, On
Range: Fail, OK
Range: Fail, OK
6.2 STATUS
ÖØ
SETTINGS
6
6.2.12 FLEX STATES
6.2.13 ETHERNET
6-7