2.3
ES/M 2.24.1
Electr. Switch Actuator
Module, 2-fold, 24 V
2.3.1

Technical data

Power supply / Incoming supply
Outputs
Connections
Ambient temperature range
Design
CE norm
© 2004 ABB STOTZ-KONTAKT GmbH
Device technology
The 2-fold Electronic Switch Actuator Module is snapped into any module
slot of the Room Controller Basis Device. Using two semiconductor outputs,
it switches two resistive loads such as electrothermal valve drives for heating
control. The outputs are noise-free and wear-resistant. The nominal
switching voltage is 12 or 24 V.
Both the incoming supply and the internal voltage are supplied via the Room
Controller Basis Device. Contact is automatically established when the
modules are snapped in place.
– Internal supply
– Incoming supply
– 2 load circuits
– Load circuits
– Incoming supply
– Wire ranges
– Storage
– Transport
– Type of installation
– Housing, colour
– Housing dimensions (WxHxD)
– Weight
– in accordance with the EMC guideline and
the low voltage guideline
made available by the Room Controller Basis
Device, contact made via contact system on
base of module
10...30 V AC / DC
Semiconductor outputs for resistive loads
Inrush current: max. 1 A
Continuous current: max. 700 mA
1 x four-pole, plug-in screw terminal
1 x two-pole, plug-in screw terminal each for
connection and for looping through
2
0.2...2.5 mm
finely stranded
2
0.2...4.0 mm
single-core
-25 °C ... 55 °C
-25 °C ... 70 °C
For snapping into the
Room Controller Basis Device
Plastic housing, anthracite, halogen-free
49 mm x 42 mm x 93 mm
0.08 kg
9