ABB i-bus EIB Product Manual page 40

Switch actuator modules for the room controller, intelligent installation systems
Hide thumbs Also See for i-bus EIB:
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
© 2004 ABB STOTZ-KONTAKT GmbH
Project design and programming
Object: "Telegr. status byte": 1 byte (non EIS)
This object is only visible for the Electronic Switch Actuator Modules ES/M
2.x.1. It provides more detailed information about the operating state of the
device. The object value is sent when there is a change in the value.
Bit
Meaning
0 (LSB)
Overload (e.g. short circuit) at output A
1
Overload (e.g. short circuit) at output B
2
Not used, always "0"
3
Not used, always "0"
4
Not used, always "0"
5
Not used, always "0"
6
Supply voltage available
7 (MSB)
Type of supply voltage: 0 = AC; 1 = DC
A detailed table to classify the object value can be found in section 5.1.
Object: "Permanent ON": 1 bit (EIS1)
If this object receives the value "1", the output is permanently switched on
when the staircase lighting function is used. When permanent ON has
finished (telegram value "0"), the reaction can be parameterised.
Object: "Warning stairc. lighting": 1 bit (EIS1)
This object can be enabled in the "Staircase lighting" time function via the
parameters. During the warning time, the object receives the value "1"
before the staircase lighting time has elapsed. The user can thus be warned
for example by triggering a push button LED.
Object: "Duration of staircase lighting": 2 byte (DPT7.005)
The staircase lighting time (t
indicated in seconds. On recovery of the supply voltage, the object value is
overwritten by the originally parameterised value.
This object is visible if "yes" is entered under the parameter Duration of
staircase lighting can be changed by object.
Note:
The staircase lighting time cannot be shorter than the warning
time. The warning is always carried out by switching on/off
briefly.
Objects: "Call preset 1/2" and "Call preset 3/4": 1 bit (EIS1)
Retrieves a parameterisable switching state. The object values "0" or "1"
retrieve the switching states "Preset1" or "Preset2" and "Preset3" or
"Preset4".
It is possible to set a further option for "Preset1" or "Preset3" that the status
is restored before retrieving "Preset2" or "Preset4" or that the switching state
is reset to the parameterised value. This is advisable if preset2 or preset4
can be stored.
Objects: "Set preset 1/2" and "Set preset 3/4": 1 bit (EIS1)
Stores the current switching state of the output as the new preset value.
Telegram value "0" stores preset1, telegram value "1" stores preset2.
If the special function "restore old value before preset2" or "restore
parameterised value of preset2" is assigned to preset1, the telegram value
"0" is ignored.
) can be modified via this object. The time is