Parameter window:
"Monitoring"
© 2004 ABB STOTZ-KONTAKT GmbH
Project design and programming
The cyclic monitoring of the room thermostat via the objects "Control value
heating" and "Control value cooling" can be enabled here. As soon as the
objects are not received for a certain period, the device switches to fault
mode (object "Telegr. fault thermostat" = "1").
Cyclic monitoring may only be enabled if the room thermostat sends the
objects "Heating" and/or "Cooling" cyclically.
Parameter: "Cyclic monitoring time of room thermostat"
This parameter is visible if cyclic monitoring has been enabled. The cyclic
monitoring time is set here.
Parameter: "Fan speed during fault of room thermostat"
This parameter is visible if cyclic monitoring has been enabled. It defines
which fan speed and valve position are triggered during fault mode.
Parameter: "Valve position during fault of room thermostat"
It can be set here whether heating or cooling should be carried out in fault
mode or whether the current setting should be maintained.
The parameter is visible, if a 4-pipe system is used.
Parameter: "Enable object 'Telegr. fault'"
The object "Telegr. fault thermostat" which can indicate the failure of the
room thermostat can be enabled in this parameter.