4.5.6
Parameter window:
"Speed limitation"
4.5.7
Parameter window:
"Forced operation"
© 2004 ABB STOTZ-KONTAKT GmbH
Project design and programming
Parameter: "Highest speed during active limitation"
The highest fan speed during active speed limitation is set here (see object
"Speed limitation").
During a forced operation, the actuator triggers a freely adjustable forced
position. This has the highest priority i.e. it is not modified by a valve purge
or safety position. The forced operation can be activated via the object
"Forced operation" = ON and deactivated via "Forced operation" = OFF.
Parameter: "Fan speed during forced operation"
This parameter defines which fan speed and valve position are triggered
during the forced operation.
Parameter: "Valve position during forced operation"
The valve position triggered by the actuator during forced operation is
defined in this parameter. The switch cycle time t
in the parameter "PWM cycle time for continuous control".
of the control is defined
CYC
57