Mitsubishi Electric MELSEC iQ-R Series User Manual page 141

Ethernet/ip network interface module, application
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■'EtherNet/IP data link continuation specification request' (Un\G16635) is set
Performed by the RJ71EIP91
'EtherNet/IP data link
continuation specification
request' (Un\G16634)
'EtherNet/IP data link
continuation specification
state' (Un\G16635)
'EtherNet/IP communication
OFF
start request' (Y10)
'EtherNet/IP communication
OFF
in process' (X10)
EtherNet/IP communications
(1) Parameter setting
PING test execution request (Y12)
Turn this signal off and on to execute a PING test.
• Off to on: PING test execution request
• On to off: PING test completion request
Turning on 'PING test execution request' (Y12) clears 'PING test result area' (Un\G27908 to Un\G27911).
Turning off 'PING test execution request' (Y12) turns 'PING test completion' (X12) on and off.
Performed by the RJ71EIP91
Performed by the program
'PING test execution request'
OFF
(Y12)
'PING test completion' (X12)
OFF
'PING test request area'
(Un\G27904 to Un\G27907)
'PING test result area'
(Un\G27908 to Un\G27911)
Stop specification request
Stop specification status
(1)
ON
OFF
ON
OFF
Communication enabled
ON
Request data setting
0
Continuation setting request
Continuation setting status
(1)
ON
OFF
ON
OFF
Communication enabled
OFF
ON
OFF
PING test result
APPX
139
Appendix 2 I/O Signals
A