Section 5 BUFFER MEMORY
5.3.6
Phase 1 current (Un\G202, 203), Phase 2 current (Un\G204, 205),
Phase 3 current (Un\G206, 207)
The electric current (present value) of each phase is stored.
(1)
Details of stored data
(a) Storage format
Data is stored as double-word 32-bit unsigned binary in the buffer memory.
・Data range: 0 to 99999990 (0 to 99999.990 A)
* Restrictions for measured data including resolution and measuring range, refer to "3.4.1".
(b) Unit
A *Unit is fixed.
-3
×10
(c) Update timing
It will be updated every measuring cycle. For measuring cycle, refer to "5.2.12".
5.3.7
Phase 1 current demand (Un\G210, 211), Phase 2 current demand (Un\G212, 213),
Phase 3 current demand (Un\G214, 215)
Stores the electric current (present value) at each phase that is measured based on the moving average for
the duration of time configured in the electric current demand time (Un\G3).
(1)
Details of stored data
(a) Storage format
Data is stored as double-word 32-bit unsigned binary in the buffer memory.
・Data range: 0 to 99999990 (0 to 99999.990 A)
* Restrictions for measured data including resolution and measuring range, refer to "3.4.1".
(b) Unit
-3
A *Unit is fixed.
×10
(c) Update timing
It will be updated every measuring cycle. For measuring cycle, refer to "5.2.12".
5.3.8
Average current (Un\G218, 219)
Stores the Average current.
For procedure for storing the Average current using phase wire system, refer to "3.4.1(2)".
(1)
Details of stored data
(a) Storage format
Data is stored as double-word 32-bit unsigned binary in the buffer memory.
・Data range:0 to 99999990 (0 to 99999.990 A)
* Restrictions for measured data including resolution and measuring range, refer to "3.4.1".
(b) Unit
A *Unit is fixed.
-3
×10
(c) Update timing
It will be updated every measuring cycle. For measuring cycle, refer to "5.2.12".
73
RE81WH