Section 6 SETTING AND PROCEDURE FOR OPERATION
6.4

Parameter setting

This section explains setting from GX Works3 necessary to use RE81WH. Before performing this setting, install
GX Works3 and connect the Management CPU with the PC using a USB cable. For details, refer to the "manual
of CPU module". For operation the GX works3, refer to "GX Works3 Operating Manual".
* For the screen and operation, description using an example of RE81WH(version B).
Supplement
To addition the module, parameter setting and auto refresh, write the settings to the CPU module,
and operation the following.
Settings
Addition the module
Auto refresh
Parameter setting
Reset the CPU module (OFF → ON) or power on the programmable
controller again.
(1) Reset the CPU module (OFF → ON) or power on the programmable
controller again.
(2) Operate the CPU module "STOP → RUN".
(3) Operate the operating condition setting request (Yn9) "ON → OFF".
Operation
112
RE81WH