Mounting And Removing The Module - Mitsubishi Electric MELSEC iQ-R Series User Manual

Energy measuring module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Section 6 SETTING AND PROCEDURE FOR OPERATION
6.2

Mounting and removing the module

6.2.1
How to mount to the base unit
1. When a cap is attached to the module connector of the base unit,
remove it.
2. Place the concave part (1) of the module on to the guide (2) of the
base unit.
3. Push in the module until the module fixing hook (3) snaps into
place.
4. Check that the module fixing hook (3) hangs the base unit and the
module is mounted on the base unit securely.
● Mount to the base of MELSEC iQ-R series.
● When mounting the module, make sure to insert the protruding portions for fixing the module into the
holes on the base unit. In those case, insert it securely so that the protruding portion of the module does
not come off of the holes. Do not forcibly mount the module, otherwise the module may be damaged.
● When installing the module at a vibrating area with strong impact, tighten the module to the base unit
using screws.
Module-fixing screws: M3 x 12mm (Prepare them by yourself)
Screw size
Module-fixing screws (M3 x 12mm)
● Mounting and detaching the module and the base unit should be performed 50 times or less (to
conform to JIS B3502). If the count exceeds 50 times, it may cause a malfunction.
Caution
Tightening torque range
0.36 – 0.48 N・m
99
RE81WH
(3)
(1)
(2)

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Melsec re81wh