Section 6 SETTING AND PROCEDURE FOR OPERATION
6.4.4
Integrated value set function
This function is to set integrated value (electric energy (consumption, regeneration) and reactive energy
(consumption lag)) to any value. If you want to clear integrated value, set it to 0.
(1)
Setting procedure
Below diagrams are examples of setting the RE81WH as "Mounting slot No.: 0", "Start I/O No.: 0000".
The start I/O No. varies depending on the mounting slot No..
(a) Open the "Watch" window.
Select [View] → [Docking Window] → [Watch 1].
(b) Input "Un\G51", "Un\G52", "YnC" and "XnC" for column of [Name].
(The "n" is start I/O No. of target module.)
Example: When start I/O No. is 0040,
Input "Y49" in device name.
(c) Change the [Data Type] of [Un\G52].
Double-click the [Data Type] column of [Yn9] row, and select the "Double Word [Unsigned]/Bit String
[32-bit]" from pull-down list.
(d) Right-click on the [watch 1] window → select [Start Watching] from the shortcut menu.
Display the value of programmable controller.
123
RE81WH