Section 8 TROUBLESHOOTING
Error code
Error
(HEX)
level
180Ah
Low
180Bh
Low
180Ch
Low
180Dh
Low
Low
180Eh
180Fh
Low
1841h
Low
0000h
-
* Also check that it is set in decimal.
Table 8.1-2 List of error codes (2/2)
Descriptions
Alarm 1 delay time (Un\G15) is
set out of range.
Alarm 2 delay time (Un\G25) is
set out of range.
Integrated value setting value
(Un\G52, 53) is set out of range.
Primary voltage of VT is set out
of range.
Secondary voltage of VT is set
out of range.
Primary current of CT is set out
of range.
Period
of
measured
acquisition clock is set out of
range.
Normal
Action
Set alarm 1 delay time within the
range* of 0 to 300 (seconds).
Set alarm 2 delay time within the
range* of 0 to 300 (seconds).
Set electric energy preset value
within
the
range*
999999999 in the double word
format (32-bit integer).
Set primary voltage of VT within
the range* of 0 to 6600 (V).
However, this setting cannot set 0
(Any
voltage)
voltage (Un\G1) is 0.
Set secondary voltage of VT within
the range* of 0 to 220 (V).
However, this setting cannot set
0(Any
voltage)
voltage (Un\G1) is 0.
Set primary current of CT within
the range* of 0 to 6000 (A).
However, this setting cannot set 0
(Any current (EMU-CT5-A)) or
1000 (Any current (EMU2-CT5))
when primary current (Un\G2) is 0.
data
Set period of measured data
acquisition clock within the range*
of 10 to 10000 (ms).
-
136
RE81WH
Reference
5.2.9
5.2.9
of
0
to
5.2.10
5.2.2
when
primary
5.2.2
when
primary
5.2.3
5.2.12
-