Mitsubishi Electric MELSEC iQ-R Series User Manual page 63

Energy measuring module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Section 5 BUFFER MEMORY
Table 5.2.3-1 Setting value of Primary current and primary current of CT (2/2)
Primary current
(Un\G2)
Setting
Description
value
1000
Any current
1001
50A
1002
100A
1003
250A
1501
5/5A
1502
6/5A
1503
7.5/5A
1504
8/5A
1505
10/5A
1506
12/5A
1507
15/5A
1508
20/5A
1509
25/5A
1510
30/5A
1511
40/5A
1512
50/5A
1513
60/5A
1514
75/5A
1515
80/5A
(b) Operating condition setting request (Yn9) from OFF to ON to enable the setting.
(Refer to "4.2.2(5)")
(2)
Default value
Primary current (Un\G2) is set to "2: 100 A".
Primary current of CT (Un\G7) is set to "0".
Primary
current of
Current sensor
CT
(Un\G7)
1~6000
EMU2-CT5
EMU-CT50
EMU-CT100
EMU-CT250
0~6000
(However,
this setting
is disabled)
EMU2-CT5
Primary current
(Un\G2)
Setting
Description
value
1516
100/5A
1517
120/5A
1518
150/5A
1519
200/5A
1520
250/5A
1521
300/5A
1522
400/5A
1523
500/5A
1524
600/5A
1525
750/5A
1526
800/5A
1527
1000/5A
1528
1200/5A
1529
1500/5A
1530
1600/5A
1531
2000/5A
1532
2500/5A
1533
3000/5A
1534
4000/5A
1535
5000/5A
1536
6000/5A
62
RE81WH
Primary
current of
Current sensor
CT
(Un\G7)
0~6000
(However,
EMU2-CT5
this setting
is disabled)