Record Naming - GE DR60 Technical Manual

Table of Contents

Advertisement

6.2

Record Naming

68
COMTRADE records in the DR60 are comprised by the ".cfg" and ".dat" files described in
the standard.
Records are named using the COMNAME methodology, according to IEEE C37.232-
2011, Common Format for Naming Time Sequence Data Files (COMNAME).
Fault, Disturbance, Steady-state, and Sequence of Events records are named as follows:
STARTDATE,STARTTIME,TIMECODE,STATIONID,DEVICEID,COMPANY,DURATION.
STARTDATE,STARTTIME,TIMECODE,STATIONID,DEVICEID,COMPANY,DURATION.
The table below describe each parameter in the file name.
Parameter
STARTDATE
STARTTIME
TIMECODE
STATIONID
DEVICEID
COMPANY
Format
yymmdd
hhmmssuuuuuu
soohmm
included only when fractional hours
Equipment identifier, configurable
CFG
DAT
Description
Record's start date
(year, mounth, day)
Record's start time
(hour, minutes, seconds,
microsseconds)
Indication of timezone offset
(the last three characters are
are in use)
Location of the equipment,
configurable in:
G
> L
ENERAL
OCATION
(up to 255 characters)
in:
G
> I
ENERAL
DENTIFIER
(up to 61 characters)
Equipment owner description,
configurable in:
G
> O
ENERAL
WNER
(up to 255 characters)
DR60-TM-EN-2A
DR60

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents