Table of Contents

Advertisement

DR60
5.5.3
Ethernet Network Synchronism Recommendations
5.6

Recording

51
Internal clock: sets the DR60 to work with no external source of sync. The internal
clock configuration is carried out through the web interface described in the
Monitoring Web Interface section.
In order to obtain the best synchronism performance in an Ethernet network, the
following configuration is recommended.
PTP Power Profile (IEEE C37.238);
o
Delay mechanism: Peer-to-Peer ( P2P)
This means that ALL equipment (Switches, GPS clocks, DR60s, Relays, Bay
Controllers, and so on) must be PTP-aware.
o
Mapped as Ethernet ( Layer 2 – L2) messages
This means that ALL equipment (Switches, DR60s, Relays, Bay Controllers, and so
on) must be PTP-aware.
o
One-step (preferred) or Two-step operation
Time is stamped preferentially at hardware.
Max number of hops: 16
Max error introduced by hop: 50ns
Max error in slave: 1us
Multicast filtering or VLAN segregation shall be configured in the managed switches,
otherwise the DR60 might present instable and undesirable behavior in its applications
and synchronism.
This configuration tab options to enables/disables the waveform, disturbance,
continuous disturbance and SOE recorder and their parameters.
The following configuration parameters are available:
Waveform recorder: Enables/disables the recorder.
Pre trigger time: configures the recording time duration before the waveform
recorder trigger.
Post trigger time: configures the recording time duration after threshold is
desensitized.
Maximum time: configures the maximum time of the record.
Disable for: disables temporarily the recorder if various triggers repeat within
a period of time.
Sample rate: selects the sampling rate of the recorder (256 or 512 s/c).
Retrigger: Enables and disables the retrigger. Refer to Records Chapter for
information on retrigger functioning.
DR60-TM-EN-2A