Chapter 11: Wiring Diagrams; Connection Diagrams Of The Voltage Inputs - GE DR60 Technical Manual

Table of Contents

Advertisement

DR60
Digital Recorder

Chapter 11: Wiring Diagrams

1

Connection Diagrams of the Voltage Inputs

DR60-TM-EN-2A
This chapter contains the all the possible wiring diagrams for the analogue inputs. For
further details on the inputs, refer to Installation Chapter
The DR60 provides the capability for making some different voltage signal connections
for a 3-phase circuit:
Connection diagram of the voltage inputs
4-element connection: in this
case, the values shown are
equivalent to the voltages of
phases A, B and C, and to the
neutral voltage applied to the
equipment.
3-element (Phases A, B and C)
connection: in this case, the
fourth element is derived of the
values measured by the other
elements. The three elements are
equivalent to the values applied to
the equipment