Recording Times By Trigger - GE DR60 Technical Manual

Table of Contents

Advertisement

3.2

Recording Times by Trigger

66
Basic
Voltage total harmonic distortion
Fundamental
Frequency
Fundamental
Voltage (RMS)
Fundamental
Current (RMS)
Fundamental
Phase active power
Fundamental
Phase reactive power
Fundamental
Phase apparent power
Others
Phase power factor
Basic
Current total harmonic distortion
Basic
Voltage total harmonic distortion
Transducer (magnitude)
GOOSE inputs
Digital inputs
Digital outputs
Once triggered, the following parameters are considered by the disturbance recorder:
Parameter
Pre-fault time (t
)
pre
Post-fault time (t
)
pos
Maximum Record time (t
The Maximum Record time configures the maximum duration that the register can
reach. If consecutive retriggers or a sustained fault happens, the Maximum Record time
establishes the limit of time that the COMTRADE file will register.
The maximum duration of the disturbance record is 60 minutes.
Allowed values
0 ... 2 min
0 ... 60 min
)
1 ... 60 min
max
MET/MHAI.ThdPhV.phsC.cVal.mag.f
MMXN
MET/MMXN.Hz.mag.f
MET/MMXN.Vol.mag.f
MET/MMXN.Amp.mag.f
MET/MMXN.Watt.mag.f
MET/MMXN.VolAmpr.mag.f
MET/MMXN.VolAmp.mag.f
MET/MMXN.PwrFact.mag.f
MHAN
MET/MHAN.ThdAmp.mag.f
MET/MHAN.ThdVol.mag.f
TGSN
MET/TGSN.GenSv.instMag.f
Digital inputs
DIG/GOOSEGGIO1
DIG/DIGITALGGIO1
DIG/OUTPUTGGIO1
Increment
DR60
0.1 min
0.1 min
0.1 min
DR60-TM-EN-2A