Type Tests Dr60 - GE DR60 Technical Manual

Table of Contents

Advertisement

1.13

Type Tests DR60

DR60-TM-EN-2A
As tested per 60068-2-2
Enclosure Protection IEC 60529
EMC tests were performed according to IEC 60255-26 referring to the following
standards
Test
Standard
Electrostatic
IEC 61000-4-
discharge
IEC 61000-4-
RF immunity
Fast transient
IEC 61000-4-
disturbance
IEC 61000-4-
Surge immunity
Conducted RF
IEC 61000-4-
immunity
Power magnetic
IEC 61000-4-
immunity
Voltage dip,
IEC 61000-4-
short
11:2004
interruptions and
IEC 61000-4-
voltage variation
29:2000
immunity tests
+55°C
IP20
Type Tests DR60
6kV contact / 8KV air (level 3)
2:2008
3:2006
4:2012
5:2005
6:2008
30A/m continuous - 300A/m @ 1s (level 4)
8:2009
Test level: 0% residual voltage
Test level: 40% residual voltage
Test level: 70% residual voltage
Level
10 V/m (level 3)
Zone A
4kV / 5kHz
Zone A
Differential mode: 2 kV
Common mode: 4 kV
0.15MHz to 80MHz
10V/rms
AC and DC voltage dips
Duration time
a.c.: 1 cycle
d.c.: 16.6ms
Duration time
a.c.: 12 cycle
d.c.: 200ms
Duration time
a.c.: 30 cycle
d.c.: 500ms
DR60