Binary Outputs; Environmental Conditions - GE DR60 Technical Manual

Table of Contents

Advertisement

1.11

Binary Outputs

1.12

Environmental Conditions

DR60-TM-EN-2A
Description
Switching Voltage
Maximum continuous current
Maximum voltage
Making Capacity
Breaking Capacity
Operation time
Dropout time
Burden
Withstand
voltages
contacts
Permissible short time value for 1s
Operating temperature range
Maximum operating altitude
Relative humidity
As tested per 60068-2-1
Digital outputs specifications
Dry contact relay, normally open
250 V ( AC and DC)
5 A
300 (AC and DC)
15 A, 4 sec
40 W Resistive, 25 W/VA L/R = 50
< 5 ms
< 15 ms
Per energized output relay: ~50mA
@12V [600mW]
across
open
1000V rms
30A
Environmental Conditions
- 40 ... +55 °C (–40°F to +131°F)
2000 m (6560 ft)
5 ... 95 %, noncondensing
-40°C
DR60
113

Hide quick links:

Advertisement

Table of Contents
loading