DR60-TM-EN-2A
Conducted RF
IEC 61000-4-16:
immunity, 0 to
150 kHz
IEC 61000-4-
Voltage ripple
17:1999
Damped
IEC 61000-4-
oscillatory wave
18:2006
immunity test
---
Gradual Startup
Radio-frequency
CISPR11:2009
disturbance
Radio
CISPR22:2008
disturbance
AC and DC voltage interruptions
Test level: 0% residual voltage
Differential mode: 150 V rms
2009
Common mode: 300 V rms
Test level: 15 % of rated d.c. value
Test frequency: 120Hz, sinusoidal
Voltage oscillation frequency: 1MHz
Differential mode: 1kV peak voltage;
Common mode 2,5kV peak voltage
Shut-down ramp: 60s
Radiated emission below 1GHz
40 dB(µV/m) quasi peak at 10 m
230 MHz to 1 000 MHz
47 dB(µV/m) quasi peak at 10 m
Radiated emission above 1GHz
56 dB(µV/m) Average
76 dB (µV/m) peak at 3m
60 dB(µV/m) Average
80 dB (µV/m) peak at 3m
Duration time
a.c.: 300 cycles
d.c.: 5s
Zone A
Test voltage
waveform.
Power off: 5m
Start-up ramp: 60s
class A
30 MHz to 230 MHz
1 GHz to 3 GHz
3 GHz to 6 GHz
DR60