ABB 2600T Series Operating Instruction page 64

Multivariable pressure transmitters
Hide thumbs Also See for 2600T Series:
Table of Contents

Advertisement

Error code
Displayed message
F109.003
Process Temperature
Sensor Fail
F110.002
Sensor Temperature Fail
F112.001
Static Pressure Sensor Fail
F114.000
P-dP Sensor Fail
F116.023
Electronic Memory Failure
Sensor Memory Fail
F118.017
F120.016
Sensor Invalid
M014.037
Configuration Error
M016.039
PILD-Changed Op.
Conditions
64 OI/266CXX/266JXX/HART-EN Rev. B | 266CRx, 266JRx, 266CSx, 266JSx
Possible cause
A/D converter error of the temperature
sensor.
Wire break of wrong Pt100 connection.
The reference voltage for the temperature
measurement is not correct.
The difference between the main channel
and the reference measurement is outside of
tolerance.
Error in the current circuit for scanning the
temperature.
Error in the current circuit for scanning the
static pressure.
Mechanical damage on the measuring cell.
Measuring cell loses filling fluid, diaphragm is
torn, sensor damaged.
Electronic memory is damaged.
Measuring cell memory damaged.
The measuring cell signal is not updated
correctly due to an electronics error, a
measuring cell error or a poorly connected
measuring cell cable.
The model / the version of the measuring cell
is no longer compatible with the connected
version of the electronics.
See the operating manual for possible cause
of the error.
The process conditions have changed to
such an extent that new settings are required
for the PILD algorithm.
Recommended measure
Check the connection of the temperature
electronics. Temperature electronics must
be replaced if the problem persists.
Check the Pt100 connections and process
conditions.
The PCB for the temperature measurement
should be replaced.
The measuring cell must be replaced.
The measuring cell must be replaced.
The measuring cell must be replaced.
The electronics must be replaced.
The measuring cell must be replaced.
Check the cable connection and replace
measuring cell if the problem persists.
The measuring cell must be replaced.
Use HART configurator (DTM – handheld
terminal) to correct the configuration.
New training is required for this new
process condition.
Transmitter
reaction
Alarm
current
Analog
alarm signal
Analog
alarm signal
Analog
alarm signal
Analog
alarm signal
Alarm
current
Analog
alarm signal
None
None