Information level (operator menu)
On the information level, the operator menu can be used to
display diagnostic information and choose which operator
pages to display.
Process display
1. Use
to go to the information level.
Operator menu
Diagnostic
Operator Page
Signals View
Back
Select
2. Use
or
select a submenu.
3. Confirm the selection with
Menu
Description
... / Operator Menu
Diagnostic
Display of the current alarms and messages.
Operator Page
Switches to the process display.
Signals View
Selects the "Signals View" submenu (only for
service purposes).
40 OI/266CXX/266JXX/HART-EN Rev. B | 266CRx, 266JRx, 266CSx, 266JSx
.
Error messages on the LCD display
If there is an error, a message consisting of a symbol and text
(e.g. Electronics) appears at the bottom of the process
display. The text displayed provides information about the area
in which the error has occurred.
Process display
Electronics
The error messages are divided into four groups in
accordance with the NAMUR classification scheme.
Symbol
Description
Error / failure
Function check
Outside of the specification
?
Maintenance required
The error messages are also divided into the following areas:
Area
Description
Process
Diagnostic messages that refer to the process
and display impairments or states.
Sensor
Alarms that indicate problems with the
measuring cell.
Electronics
Errors in the device electronics are displayed.
Configuration
Missing or faulty configuration of the transmitter
is detected.