ABB 266CRH Instructions Manual

Multivariable pressure transmitter with modbus communication
Hide thumbs Also See for 266CRH:
Table of Contents

Advertisement

A B B M E A S U R E M E N T & A N A L Y T I C S | O P E R A T I N G I N S T R U C T I O N
266CRH / 266CRT, 266CSH / 266CST
Multivariable pressure transmitter
Introduction
The multivariable transmitters in the 266CRH/CRT,
266CSH/CST are used for differential pressure flow
measurements.
Apart from pressure- and / or temperature-
dependent changes to the density of the fluid, the
parameters such as the discharge coefficient,
thermal expansion of pipelines and primary device
and the Reynolds number are also corrected. It can
also be used for DP level measurement if density
compensation is necessary due to process
temperature changes.
This could make any level measurement much more
reliable.
In addition to high precision, the multivariable 266
also offers the advantage that only a single device
needs to be used for the measuring point instead of
several transmitters and a flow calculator.
With Modbus communication
Measurement made easy
For more information
Additional documentation on 266CRH / 266CRT,
266CSH / 266CST is available for download free of
charge at www.abb.com/pressure.
Alternatively simply scan this code:

Advertisement

Table of Contents
loading

Summary of Contents for ABB 266CRH

  • Page 1 A B B M E A S U R E M E N T & A N A L Y T I C S | O P E R A T I N G I N S T R U C T I O N 266CRH / 266CRT, 266CSH / 266CST...
  • Page 2: Table Of Contents

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Table of contents Change from one to two columns Installation ..............16 Safety ................4 Mounting ................. 16 General information and instructions ........4 IP rating ................16 Warnings ..................
  • Page 3 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Commissioning ............36 11 Repair ............... 82 Safety instructions ..............36 Safety instructions ..............82 General Notes ................. 36 Spare parts ................82 Zero point correction following installation ..... 36 Opening and closing the housing ........
  • Page 4: Safety

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 1 Safety General information and instructions Warnings These instructions are an important part of the product and The warnings in these instructions are structured as follows: must be retained for future reference.
  • Page 5: Intended Use

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Intended use Notes on data safety The 266CRH / 266CRT, 266CSH / 266CST multivariable pressure This product is designed to be connected to and to transmitters measure the level or the mass flow of gases, communicate information and data via a network interface.
  • Page 6: Use In Potentially Explosive Atmospheres

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 2 Use in potentially explosive atmospheres Change from one to two columns Ex marking FM (USA and Canada) Devices in hazardous atmospheres with or without integrated digital display.
  • Page 7: Ex Explosion Protection Aspects (Europe And International)

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Ex explosion protection aspects (Europe and International) Type of protection: Ex d Certifications ATEX (Code E2) According to ATEX Directive (European Directive 2014/34/EU) and applicable European standards which assure compliance...
  • Page 8 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 2 Use in potentially explosive atmospheres … Ex explosion protection aspects (Europe and International) Tank Silo Code E9 Ex-Marking IECEx Ex db IIC T6 Ga/Gb Ex tb IIIC T85 °C Db FM Approvals Certificate IECEx FME 16.0002X...
  • Page 9: Type Of Protection: Ex N Certifications Atex (Code E3) And Iecex (Code Er)

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Type of Protection: Ex n Certifications ATEX (Code E3) and IECEx (Code ER) Code E3 Ex-Marking ATEX Code E3 Ex-Marking IECEx II 3 G Ex nA IIC T4 ... T6 Gc IP67 Ex nA IIC T4 ...
  • Page 10: Ex Explosion Protection Aspects (United States And Canada)

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 2 Use in potentially explosive atmospheres Ex Explosion protection aspects (United States and Canada) According to Factory Mutual standards for the assurance of Type of protection: Explosion-proof Certification...
  • Page 11: Type Of Protection: Explosion Proof Certification

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Type of protection: explosion proof Certification (Code ET) The 266 transmitters have FM certification for the following hazardous location protections: Code ET ratings Non-Incendive Class I, Division 2, Groups ABCD, T*...
  • Page 12: Design And Function

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 3 Design and function Components of the pressure transmitter Measuring range limits and span limits The data sheets for the Series 2600T multivariable transmitters contain all the information concerning the measuring range and measuring span of the individual models, as well as the sensor code.
  • Page 13: Product Identification

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 4 Product identification Name plate Calib. Range 2600T Number PRESSURE TRANSMITTER 2600T AAAAAAAAAAAAAAAAAAAAAAAAA BBBBBBBBBBBBBBBBBBBBBBBB CCCCCCCCCCCCCCCCCCCCCCC DDDDDDDDDDDDDDDDDDDDDDDD EEEEEEEEEEEEEEEEEEEEEEEE M11199 A Name plate 9 Set span B Special data plate with Ex-marking...
  • Page 14: Marking According To Pressure Equipment Directive

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 4 Product identification … Name plate Marking according to Pressure Equipment Directive The device is identified via the signs (plates) presented in Figure 3. Devices with PS > 200 bar (20 MPa) Devices with a permissible pressure of PS >...
  • Page 15: Transport And Storage

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 5 Transport and storage Transport safety instructions Storing the device Observe the following instructions: Bear the following points in mind when storing devices: • Do not expose the device to humidity during transport.
  • Page 16: Installation

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 6 Installation Mounting Before installing the pressure transmitter, check whether the IP rating device design meets the requirements of the measuring point The housing of the 266CRH / 266CRT, 266CSH / 266CST...
  • Page 17: Venting / Draining Transmitters Without Diaphragm Seals

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Mounting position Venting / draining transmitters without diaphragm The pressure transmitter can be attached directly on a valve seals manifold provided for flange installation. Optionally a fastening bracket for wall or pipe installation WARNING (2 in pipe) is available as an accessory.
  • Page 18: Mounting Dimensions - Model 266Crx

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation Mounting dimensions – Model 266CRx Transmitter with barrel housing 29 (1.14) 56 (2.21) 53 (2.09) 18 (0.71) 18 (0.71) 91 (3.58) 54 (2.13) 54 (2.13) 71(2.80)
  • Page 19: Transmitter With Barrel Housing And Mounting Bracket, For Vertical Or Horizontal Mounting On 60 Mm (2 In) Pipe

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Transmitter with barrel housing and mounting bracket, for vertical or horizontal mounting on 60 mm (2 in) pipe 29 (1.14) 56 (2.21) 53 (2.09) 18 (0.71) 18 (0.71) 91 (3.58)
  • Page 20: Transmitter With Barrel Housing And Flat Bracket, For Vertical Or Horizontal Mounting On 60 Mm (2 In) Pipe

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation … Mounting dimensions – Model 266CRx Transmitter with barrel housing and flat bracket, for vertical or horizontal mounting on 60 mm (2 in) pipe 91 (3.58)
  • Page 21: Mounting Dimensions - Model 266Csx

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Mounting dimensions – Model 266CSx Transmitter with barrel housing – horizontal flanges 29 (1.14) 18 (0.71) 18 (0.71) 56 (2.21) 53 (2.09) 91 (3.58) 9 (0.35) 60 (2.36)** 72 (2.83)***...
  • Page 22: Transmitter With Barrel Housing - Vertical Flanges

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation … Mounting dimensions – Model 266CSx Transmitter with barrel housing – vertical flanges 110 (4.33) 53 (2.09) 28 (1.10) LCD (L1) 91 (3.58) 24 (0.95) TTG-LCD (L5) 18 (0.71)
  • Page 23: Transmitter With Mounting Bracket, For Vertical Or Horizontal Mounting On 60 Mm (2 In) Pipe Pipe

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Transmitter with mounting bracket, for vertical or horizontal mounting on 60 mm (2 in) pipe pipe 29 (1.14) 18 (0.71) 18 (0.71) 56 (2.21) 53 (2.09) 91 (3.58) 60 (2.36)²i...
  • Page 24: Transmitter With Flat Bracket, For Vertical Or Horizontal Mounting On 60 Mm (2 In) Pipe

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation … Mounting dimensions – Model 266CSx Transmitter with flat bracket, for vertical or horizontal mounting on 60 mm (2 in) pipe 29 (1.14) 18 (0.71) 56 (2.21) 53 (2.09)
  • Page 25: Opening And Closing The Housing

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Opening and closing the housing Adjusting the transmitter position Transmitter housing DANGER Danger of explosion if the device is operated with the DANGER transmitter housing or terminal box open!
  • Page 26: Rotate The Lcd Display

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation Connecting impulse lines … Adjusting the transmitter position Rotate the LCD display WARNING If the device has an integral LCD display, this can be mounted in...
  • Page 27: Process Connections

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Mounting recommendations The arrangement of the impulse lines depends on the respective Process connections measurement application. Flow measurement of steam (condensible vapor) or clean liquids M10801-01 1 Screws...
  • Page 28 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation … Mounting recommendations To commission the transmitter, operate the valves in the Flow measurement of gas or liquid with solids in following sequence: suspension 1.
  • Page 29: Fill Level Measurement On Closed Tanks

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Fill level measurement on closed tanks Fill level measurement on open tanks with fluids Non-condensing measuring medium (dry leg) H High pressure side 1 Liquid L Low pressure side Figure 21: Level measurement on open tanks •...
  • Page 30: Fill Level Measurement On The Steam Boiler (Drum Water Level)

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation … Mounting recommendations Temperature measurement Fill level measurement on the steam boiler • Mount the temperature sensor in the downstream pipe of (drum water level) the primary element.
  • Page 31: Electrical Connections

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Electrical connections Safety instructions for electrical installation General The relevant directives must be complied with for the electrical DANGER installation! Explosion hazard Because the transmitter cannot be switched off, surge...
  • Page 32: Cable Entries

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation … Electrical connections Cable entries Grounding The electrical connection is made via cable entries with a ½ in NPT or M20 ×1.5 thread. Note...
  • Page 33: Electrical Data For Inputs And Outputs

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Note – Connection of a Pt100 temperature sensor Modbus communication For the purpose of simulation, a 178 resistor [206 °C (402.8 °F)] with 2 jumpers has been installed between Note the terminals for the Pt100 connection.
  • Page 34 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 6 Installation … Electrical connections Cable specification The maximum cable length depends on the type of cable used. The maximum permissible length depends on the baud rate, the...
  • Page 35: Connection On The Device

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Connection on the device Modbus 9...30 V DC A(+) COMM. B(-) SURGE INSIDE M11189 1 Terminals for Modbus® interface 4 Terminals for Pt100 resistance thermometer 2 Terminal for PE / Cable Shield...
  • Page 36: Commissioning

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 7 Commissioning Safety instructions Zero point correction following installation If there is a chance that safe operation is no longer possible, NOTICE take the device out of operation and secure it against Material damage due to a magnetic field! unintended startup.
  • Page 37: Setting Precalibrated Devices

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Hardware settings Setting precalibrated devices Write protection switch Note 266Cxx transmitters do not support this function if the ‘Level measurement’ calculation function has been activated. In this case, the correction must be made using the optional LCD indicator or the DTM.
  • Page 38: Dip Switches On The Secondary Electronics

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 7 Commissioning … Hardware settings DIP switches on the secondary electronics The secondary electronics is located behind the front housing cover. The LCD indicator may have to be removed to provide Note access to the DIP switches.
  • Page 39: Parameterization Of The Device

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 7 Commissioning Configuration without integrated LCD Parameterization of the device display The transmitter is delivered preconfigured according to the Note information provided when placing the order.
  • Page 40: Configuration Via The Lcd Indicator With The Operating Buttons (Optional)

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 7 Commissioning Configuration via the LCD indicator with the operating buttons (optional) Note Easy Setup For a detailed description of the individual parameters and menus on the configuration level, please refer to Overview of ABB266 parameters on the configuration level on page 49.
  • Page 41 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Easy Setup Easy Setup Linearization Type Damping Linear 1.0000 Next Edit Next Edit 25. Use to call up edit mode. 37. Use to call up edit mode.
  • Page 42: Configuration With The Pc / Laptop

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 7 Commissioning Configuration with the PC / laptop The 266Cxx multivariable transmitters can be configured with Modbus connection of 2600T the aid of the following devices: (266xxx-MV Modbus®) via USB / RS 485-converter to...
  • Page 43: Operation

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 8 Operation Safety instructions If there is a chance that safe operation is no longer possible, The LCD indicator has capacitive operating buttons. These take the device out of operation and secure it against enable you to control the device through the closed housing unintended startup.
  • Page 44: Menu Levels

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation Menu levels Process display PI-AX-1001 Process display 278. 7 5 mbar Operator Menu Configuration Diagnostic Easy Setup Operator Page MV Setup - Mass Flow...
  • Page 45: Activation Of The Operating Menu

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Switching to the information level (operator menu) Activation of the operating menu To access the operating menu, it must first be activated. On the information level, the operator menu can be used to...
  • Page 46: Error Messages On The Lcd Display

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation Error messages on the LCD display Switching to the configuration level (parameterization) In the event of an error, a message consisting of a symbol and...
  • Page 47: Selecting And Changing Parameters

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Selecting and changing parameters Entry from table Once you have logged on to the corresponding access level, you can edit or reset the password. Reset (status ‘no password When an entry is made from a table, a value is selected from a defined’) by selecting...
  • Page 48 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Selecting and changing parameters Exiting the setup Parameter name For some menu items, values must be entered. If you don't want 12.3456 [unit] to change the parameter, you can exit the menu as described below.
  • Page 49: Overview Of Parameters On The Configuration Level

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Overview of parameters on the configuration level Note This overview of parameters shows all the menus and parameters available on the device. Depending on the version and configuration of the device, not all of the menus and parameters may be visible in it.
  • Page 50 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Overview of parameters on the configuration level MV Setup - Mass Flow MV-Calculation No Calculation Flow Level Medium Static Pressure Unit Min. Stat. Press. abs.
  • Page 51 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Meter Tube Material Carbon steel Stainless Steel, ferritic Stainless Steel, austenitic Prim. Elem. Material Bronze SnBz4 Copper E_Cu Calculation of Copper Rg 9 Brass Ms 63 Flow Unit...
  • Page 52 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Overview of parameters on the configuration level MV Setup - open Tank MV-Calculation No Calculation Flow Level Level Calculation Level Unit Steam Drum Level...
  • Page 53 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A MV Setup - closed Tank MV-Calculation No Calculation Flow Level Level Calculation Level Unit Steam Drum Level Open Tank Closed Tank Closed Tank, 2 Remote Seals Lower Level...
  • Page 54 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Overview of parameters on the configuration level A The lower fill level to be measured 3 Low pressure impulse line B The higher fill level to be measured...
  • Page 55 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A MV Setup - Steam Drum MV-Calculation No Calculation Level Flow Level Level Calculation Level Unit Steam Drum Level Open Tank Closed Tank Closed Tank, 2 Remote Seals...
  • Page 56 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Overview of parameters on the configuration level MV Setup - 2 Remote Seals MV-Calculation No Calculation Flow Level Level Calculation Level Unit Steam Drum Level...
  • Page 57 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A A The lower fill level to be measured 3 Gas above the fluid B The higher fill level to be measured 4 Capillary tube 1 Liquid level...
  • Page 58 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Overview of parameters on the configuration level Device Setup SW Write Protection Process Variable PV Type Set PV Unit Lower Range Value Upper Range Value...
  • Page 59 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A MV Overview Flow Medium Static Pressure Unit Max.Stat. Press. abs. Min. Stat. Press. abs. Bias Static Pressure Temperature Unit Min. Temperature Max. Temperature Primary Device Meter Tube Material Prim.
  • Page 60 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Overview of parameters on the configuration level Closed Tank Level Unit Lower Level Upper Level Distance process Connection Transm. mount. Pos. Display Language...
  • Page 61 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Security Display Unit Pressure Flow Mass & Volume Lower Range Value Density Upper Range Value Level Other Display Protection Custom Unit Change Password Calibration Main Pressure Sensor...
  • Page 62 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Overview of parameters on the configuration level Totalizer Input Status Start, Stop Setting Mode Normal, Batch, Forward/Reverse, Forward + Reverse, Forward - Reverse...
  • Page 63: Damping And Transmission Function

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Damping and transmission function Damping Transmission function If the output signal of the pressure transmitter is conditionally In the evaluation of the output signal of the multivariable...
  • Page 64: Description Of The Transition Function

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Damping and transmission function Description of the transition function Linear When using this function the relationship between the input value (measured value) in % of the calibrated measurement span and the output linear (i.e.: The input value of 0% corresponds to...
  • Page 65 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Square root to the third power Square root to the fifth power The square root transmission function of x3 can be used for flow The square root transmission function of x5 can be used for flow...
  • Page 66: Interface Description

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation Interface description Communication parameters Modbus message For communication to work properly, the transmission mode (and serial port parameters) must be the same for all devices on...
  • Page 67: Available Units

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Available units Table 3: Units for the mass flow For certain parameters, it is possible to choose among the Selection Code Description following units. Grams per Second...
  • Page 68 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Interface description Table 4: Units for the volume flow (continued) Table 7: Volume units Selection Code Description Selection Code Description Norm Cubic Meters per Hour...
  • Page 69: Modbus Register Tables

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Modbus register tables All registers in this document are referenced to one. The Modbus messages are referenced to zero. This means that the number of the mapped register is one higher than the number that is sent in a Modbus message frame.
  • Page 70 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Interface description 16 / 32 bit–Register Address Parameter Data type Function code 32 bit 16 bit Read Write (32 bit) Write (16 bit)
  • Page 71 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Address Parameter Data type Function code 32 bit 16 bit Read Write (32 bit) Write (16 bit) – Balance Oblique Sensor Usign8 – 06, 16 – Differential Pressure Unit (DP) Usign8 –...
  • Page 72 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Interface description Address Parameter Data type Function code 32 bit 16 bit Read Write (32 bit) Write (16 bit) – Totalizer Batch Mode Setup Usign8 –...
  • Page 73 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Optional text on display An optional text will be shown automatically on the display with sending data to the registers 1001 to 1008. It allows displaying strings in two lines written via MODBUS. The first text line is filed from register 1001 to 1004, the second text line is filed from register 1005 to 1008.
  • Page 74 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 8 Operation … Interface description Coil Register Address Parameter Function code Diagnosis condition Read Write Diagnosis Main[0] bit 0 01, 02 – Differential pressure sensor fail...
  • Page 75: Application Of The Diagnosis Main And Main 2 Registers

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Application of the Diagnosis Main and Main 2 Registers Diagnosis codes The 266CRH / 266CRT, 266CSH / 266CST has two ‘Diagnosis’ Register Error (Diagnosis Main and Main 2). The Diagnosis Main register Address (Address 411, 412) each containing 16 bits.
  • Page 76: Diagnosis / Error Messages

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 9 Diagnosis / error messages Calling up the error description Additional details about the error that has occurred can be called up on the information level. Process display Electronics 1.
  • Page 77: Error States And Alarms

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Error states and alarms Error code Displayed message Possible cause Recommended measure C042.046 Default Value as Process Substitute value for differential pressure active. The calculation will be executed with the substitute value for Value differential pressure.
  • Page 78 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 9 Diagnosis / error messages … Error states and alarms Error code Displayed message Possible cause Recommended measure F109.003 Process Temperature Sensor A/D converter error of the temperature sensor.
  • Page 79 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Error code Displayed message Possible cause Recommended measure M020.042 Replace Info The electronics or the measuring cell have been Execute replacement mode: Place switch SW 1 of the electronics replaced, but replacement mode has not been in position 1 = activate replacement mode.
  • Page 80 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 9 Diagnosis / error messages … Error states and alarms Error code Displayed message Possible cause Recommended measure S044.043 MV Calculation out of Range Flow is outside of the range.
  • Page 81: Maintenance

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 10 Maintenance Measuring cell of the multivariable Safety instructions transmitter WARNING Normally the measuring cell of the transmitter is essentially Bodily injury! maintenance-free. Transmitters with explosion protection must be either...
  • Page 82: Repair

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 11 Repair Spare parts Safety instructions Repair and maintenance activities may only be performed by WARNING authorized customer service personnel. Bodily injury! When replacing or repairing individual components, use original Transmitters with explosion protection must be either spare parts.
  • Page 83: Mounting / Dismounting The Operating Button Unit

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Mounting / dismounting the operating Removing / installing the process flange button unit 1. Unscrew the fastening screws of the process flanges in cross pattern (hexagon socket wrench AF 13 mm (0.51 in).
  • Page 84: Replacing The Measuring Cell

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 11 Repair … Removing / installing the process flange Replacing the measuring cell 6. The electronics module is connected via a ribbon cable with 1. Disconnect the transmitter from the process via the valve connector to the measuring cell;...
  • Page 85: Dismounting And Disposal

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 12 Dismounting and disposal Dismounting WARNING When the transmitter is reassembled, it can be reconfigured. The Risk of injury due to process conditions. 266 transmitter is equipped with a self-adjustment function and The process conditions, for example high pressures and thus applies the previous configuration data automatically.
  • Page 86: Disposal

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 12 Dismounting and disposal Disposal Note Products that are marked with the adjacent symbol may not be disposed of as unsorted municipal waste (domestic waste). They should be disposed of through separate collection of electric and electronic devices.
  • Page 87: Specification

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 13 Specification Note Test pressure The device data sheet is available in the ABB download area at The transmitters can withstand a pressure test with the www.abb.com/pressure.
  • Page 88: Operating Limits 266Csx

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A … 13 Specification … Operating limits 266CRx Operating limits 266CSx The table below contains the specifications for diaphragm seal Pressure limits filling fluids when used in transmitters with (a) diaphragm Gauge pressure limits seal(s).
  • Page 89: Temperature Limits °C (°F)

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Temperature limits °C (°F) Static pressure limits Environment The transmitter models 266CSX can operate within the specifications with the following limits: This is the operating temperature. Sensors...
  • Page 90: Appendix

    266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A 15 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
  • Page 91 266CRH / 266CRT, 266CSH / 266CST MULTIVARIABLE PRESSURE TRANSMITTER | OI/266CXX/MODBUS-EN REV. A Trademarks Modbus is a registered trademark of the Modbus Organization Garlock is a registered trademark of Garlock Sealing Technologies LLC Galden is a Montefluos trademark Neobee M 20 is a Stepan Company trademark...
  • Page 92 We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

This manual is also suitable for:

266csh266crt266cst

Table of Contents