CHAPTER 6
This chapter describes the installation and wiring of the master module.
6.1
Installation Environment and Position of the Master
Module
For the precautions for the installation environment and position of the master module, refer to the following.
User's Manual (Hardware Design, Maintenance and Inspection) for the CPU module used
MELSEC-L CC-Link IE Field Network Head Module User's Manual
6.2
Wiring
(1) Descriptions of terminals
Terminal
24V
0V
DP
DN
LG
INSTALLATION AND WIRING
Power supply terminal for driving the transmission circuit for the AnyWireASLINK system.
Connect to a 24VDC external power supply.
AnyWireASLINK transmission signal terminals
DP: Transmission cable (+), DN: Transmission cable (-)
Connect to the DP and DN terminals on the slave module or terminating unit.
Connected to the neutral point of the noise filter inserted between the 24V and 0V terminals.
Ground the LG terminal with the functional ground terminal (FG terminal) on the programmable
controller at a single point.
CHAPTER 6 INSTALLATION AND WIRING
Description
6
43