● A slave module address is not deleted even when the power supply of a programmable controller or a 24VDC external
power supply is turned off. The address is retained until a new address is set when a system is configured.
● For the address setting, ensure that the address occupied by the slave module does not exceed the number of
transmission points set in the master module. For the operation mode setting of the master module, refer to Page 54,
Section 7.1.2.
● In the slave module, a value between 0 and 254 can be written. (This is not an ID value.) Note that 255 cannot be set.
Doing so may cause a No ID setting error.
Model
Output slave module
Input slave module or I/O
combined slave module
56
Address (decimal)
0 to 254
0 to 254
ID (hexadecimal)
0000
to 00FE
H
H
0200
to 02FE
H
H
ID (decimal)
0 to 254
512 to 766