(b) Parameters
Each slave module has the following types of parameters:
• Device parameter (19 types)
These parameters are unique to each slave module. The contents of the parameters vary depending on
the types of slave module. For details, refer to the specifications of the slave module.
• AnyWireASLINK parameter (three types)
These parameters are common to all the slave modules connected to the AnyWireASLINK.
Name
Read/write
buffer memory area
Un\G12288+n  30
Module ID
Read
(n: 0 to 128)
1st of 48 words
Un\G12327+n  30
Status details
Read
(n: 0 to 128)
40th of 48 words
Un\G12328+n  30
Sensing level
Read
(n: 0 to 128)
41st of 48 words
Corresponding
Indicates the slave module ID.
H
• 0000
to 00FF
H
• 0200
to 02FF
H
Indicates the status of the slave module.
The status 1) to 6) of the slave module are indicated depending on ON or OFF of each bit as
below.
b15
1) Module power supply status
On: Slave module voltage drop
Off: No fault
H
2) Sensing level status
On: Sensing level drop
Off: No fault
3) I/O disconnection (ASLINKER)
On: I/O disconnection
Off: No fault
4) I/O short-circuit (ASLINKER)
On: I/O short-circuit
Off: No fault
5) I/O power supply voltage drop (isolated slave module)
On: I/O power supply voltage drop
Off: No fault
6) System reserved
Indicates the value of the connected sensor.
H
The value differs depending on the connected slave module.
(Example: An analog value of 0 to 100% is indicated for an ON/OFF sensor.)
Detailed description
: ID of output slave modules
H
: ID of an input slave module or I/O combined slave module
H
to
6)
APPENDICES
b6
b5
b3
b2
b1
b0
5)
4)
3)
2)
1)
111
A